Toshiba MMD-AP0186HP-E Service Manual page 52

Multi type
Hide thumbs Also See for MMD-AP0186HP-E:
Table of Contents

Advertisement

Target outdoor unit (SMMS-i – Series 4)
CODE No.
Indoor unit
00
data *2
01
02
03
04
05
06
08
09
FA
System unit
0A
data
0B
0C
0D
CODE No.
U1 U2 U3 U4
Individual
10 20 30 40
data 1 of
outdoor
11 21 31 41
unit *3
12 22 32 42
13 23 33 43
14 24 34 —
15
25
35
16
26
36
17
27
37
18
28
38
19
29
39
1A
2A
3A
1B
2B
3B
1C
2C
3C
1D
2D
3D
1E
2E
3E
1F
2F
3F
*1 The TF/TSA/TOA sensors are equipped only with some types of indoor units. The data does not appear for
other types.
*2 In the case of group connection, only the header indoor unit data can be displayed.
*3 The upper digit of CODE No. indicates the outdoor unit No.
*4 [(The upper digit of CODE No.) – 4] indicates the outdoor unit No.
1
, 5
... U1 outdoor unit (Header unit)
2
, 6
... U2 outdoor unit (follower unit 1)
3
, 7
... U3 outdoor unit (follower unit 2)
4
, 8
... U4 outdoor unit (follower unit 3)
*5 Only CODE No. 5• of U1 outdoor unit (Header unit) is displayed.
AMP Air Conditioning
Data
Room temperature (in control)
Room temperature (Remote controller)
Air Temperature (TA)
Coil Temperature (TCJ)
Coil Temperature (TC2)
Coil Temperature (TC1)
Discharge temperature (TF) *1
PMV
Air Suction Temperature of direct expansion
coil (TSA) *1
Outdoor Air Temperature (TOA) *1
Number of connected indoor units
Total horse power of connected indoor units
Number of connected outdoor units
Total horse power of outdoor units
Data
Detection pressure of high-pressure sensor
(Pd)
Detection pressure of low-pressure sensor
(Ps)
Discharge temperature of compressor 1
(Td1)
Discharge temperature of compressor 2
(Td2)
Discharge temperature of compressor 3
(Td3)
45
Suction Temperature (TS)
46
Coil Temperature 1 (TE1)
Coil Temperature 2 (TE2)
48
Liquid Temperature (TL)
49
Outdoor Temperature (TO)
4A
PMV1 + 2
PMV4
4C
Current of compressor 1 (I1)
4D
Current of compressor 2 (I2)
Current of compressor 3 (I3)
4F
Outdoor fan current (IFan)
Format
Unit
×1
˚C
×1
˚C
×1
˚C
×1
˚C
×1
˚C
×1
˚C
×1
˚C
×1/10
pls
×1
˚C
×1
˚C
×1
×10
HP
×1
×10
HP
Format
Unit
×100
MPa
×100
MPa
×1
˚C
×1
˚C
×1
˚C
×1
˚C
×1
˚C
×1
˚C
×1
˚C
×1
˚C
×1
pls
×1
pls
×10
A
×10
A
×10
A
×10
A
– 52 –
www.ampair.co.uk | sales@ampair.co.uk
Remote controller display example
[0024]=24 ˚C
[0150]=1500 pls
[0024]=24 ˚C
[0048]=48
[0415]=41.5HP
[0004]=4
[0420]=42HP
Remote controller display example
[0123]=1.23 MPa
[0024]=24 ˚C
[0050]=500 pls
[0135]=13.5 A

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents