Redundant communication according to IEC62439–3 Edition 1 and IEC
61850–9–2LE process bus communication are not supported in the 650
Ver 1.3 series IEDs.

Setting the station communication

To enable the IEC 61850 communication, the corresponding COM03 ports must be
activated. Port LAN1 A and LAN1 B are used for redundancy.
If COM03 is used; the following below apply. If COM05 is used; there is no redundancy
and the port is named LAN1 or (FRONT)
To enable IEC 61850 station communication:
The IEC 61850-8-1 station communication functionality must be configured in the
local HMI. Navigate to Main Menu/Configuration/Communication/TCP-IP
configuation/ETHLAN1_AB and set the OperationMode parameter to
NonRedundant(A) or, for redundant communication, to PRP(A+B).
To enable GOOSE communication, the Operation parameter for the corresponding
GOOSE function blocks (GOOSEBINRCV and GOOSEINTLKRCV) must be set to
Enabled in the application configuration.
To enable GOOSE communication via the front port the parameter GOOSE in Main
menu/Configuration/Communication/Station communication/IEC61850-8-1/
PortSelGOOSE must be set to Front. To enable GOOSE communication via rear
port the parameter PortSelGOOSE must be set to LAN1.
To enable IEC 61850 station communication:
1.
Enable IEC 61850-8-1 (substation bus) communication for port A and B.
1.1. Set values for ETHLAN1_AB.
Navigate to Main Menu/Configuration/TCP-IP configuation/
ETHLAN1_AB.
Set values for OperationMode, IPAddress and IPMask. OperationMode must
be set to NonRedundantA.
Check that the correct IP address is assigned to the port.
1.2. Enable IEC 61850-8-1 communication.
Navigate to Main menu/Settings/General settings/Communication/
Station communication/IEC 61850-8-1.
Set Operation to Enabled and PortSelGOOSE to the port used.
2.
Enable redundant IEC 61850-8-1 communication for port A and B.
2.1. Enable redundant communication.
Section 6