Mitsubishi Electric MELSEC iQ-F Reference page 37

Fx5 ethernet/cc-link ie function block
Hide thumbs Also See for MELSEC iQ-F:
Table of Contents

Advertisement

No.
Variable name
Name
(16)
pbi_uMonitorTime
Arrival monitoring
time
(17)
pbo_uResendCount
Number of resends
(18)
pbo_u4ErrTime
Error occurrence time
(19)
pbo_uErrNetworkNo
Error detection
network number
(20)
pbo_uErrStationNo
Error-detected station
number
FB details
Item
Description
Available device
Target module
CPU module
Engineering tool
Language
Ladder diagram
Number of basic steps
158 steps
The number of FB steps integrated in the program varies depending on the CPU module used, the input/output definition, and
the setting options of GX Works3. For the setting options of GX Works3, refer to GX Works3 Operating Manual.
Processing
• When i_bEN (Execution command) is turned ON, data corresponding to the send data length is sent from the send data
storage device to the specified target station address.
• If an error occurs while sending data, o_bErr (Error completion) turns ON, and the error code is stored in o_uErrld (Error
code). Refer to Page 36 Error code for details on the error codes.
FB compilation method
Macro type
FB operation
Pulsed execution (multiple scan execution type)
Data type
Range
Word [unsigned]
0, 1 to 32767
Word [unsigned]
Word [unsigned]
(0..3)
Word [unsigned]
Word [unsigned]
FX5-CCLIEF
FX5U CPU, FX5UC CPU
GX Works3 Version 1.025B or later
Description
Specify the monitoring time until completion of
processing. If the processing is not completed within the
monitoring time, data is resent until the value specified
in "maximum number of resends" is reached.
0: 10 s
1 to 32767: 1 to 32767 s
The number of resends performed (result) is stored.
Clock data at the time of error occurrence is stored.
1st word
• Upper 8 bits: Month (01H to 12H)
• Lower 8 bits: Lower 2 digits of year (00H to 99H)
2nd word
• Upper 8 bits: Hour (00H to 23H)
• Lower 8 bits: Day (01H to 31H)
3rd word
• Upper 8 bits: Second (00H to 59H)
• Lower 8 bits: Minute (00H to 59H)
4th word
• Upper 8 bits: Upper 2 digits of year (00H to 99H)
• Lower 8 bits: Day of week (00H (Sunday) to 06H
(Saturday))
The network number of the station in which an error was
detected is stored.
The station number of the station in which an error was
detected is stored.
CC-Link IE Field Network station number
• 125: Master station
• 1 to 120: Local station, remote device station,
intelligent device station, submaster station
3 CC-LINK IE FIELD NETWORK MODULE FB
3.3 M+FX5CCLIEF_Send
3
35

Advertisement

Table of Contents
loading