Mitsubishi Electric MELSEC iQ-F Reference page 10

Fx5 ethernet/cc-link ie function block
Hide thumbs Also See for MELSEC iQ-F:
Table of Contents

Advertisement

FB details
Item
Available device
Language
Number of basic steps
Processing
FB compilation method
FB operation
Timing chart of I/O signals
Restrictions or precautions
Error code
Error code
(hexadecimal)
All error code
2 FX5 ETHERNET FB
8
2.2 M+FX5UCPU-EN_ConnectionClose
Description
Target CPU
Engineering tool
Ladder diagram
136 steps
The number of FB steps integrated in the program varies depending on the CPU module used, the input/output definition, and
the setting options of GX Works3. For the setting options of GX Works3, refer to GX Works3 Operating Manual.
• When i_bEN (execution command) is turned on, this function closes a connection for data communication with target device.
• The function closes all connections if FFFF is specified for the connection number in the input argument.
• If the function fails to close even one connection among those specified to be closed, it is completed with an error.
Macro type
Pulsed execution (multiple scan execution type)
[For normal completion]
i_bEN
o_bENO
o_bOK
o_bErr
o_uErrId
[For error completion]
i_bEN
o_bENO
o_bOK
o_bErr
o_uErrId
• This FB does not include the error recovery processing. Program the error recovery processing separately in accordance
with the required system operation.
• This FB uses the SP.SOCCLOSE instruction.
• Turn off i_bEN (Execution command) after o_bOK (Normal completion) or o_bErr (Error completion) is turned on. By turning
off i_bEN (Execution command), o_bOK (Normal completion) or o_bErr (Error completion) is turned off and o_uErrId (Error
code) is cleared to 0. However, because the SP.SOCCLOSE instruction which is a pulse instruction in the FB is used, if a
write is performed while the FB is executed, the instruction may not be executed, and o_bOK (Normal completion) and
o_bErr (Error completion) may not turn on. If this happens, turn i_bEN (Execute command) from off to on again.
• This FB cannot be used in an interrupt program.
• Do not use this FB in programs that are executed only once, such as a subroutine program or FOR-NEXT loop, because
i_bEN (Execution command) cannot be turned off and the normal operation cannot be acquired. Always use this FB in
programs that can turn off i_bEN (Execution command).
• Every input must be provided with a value for proper FB operation.
• Set the module parameters in GX Works3 in accordance with the connected equipment and system. For the module
parameters, refer to the MELSEC iQ-F FX5 User's Manual (Ethernet Communication).
Description
Same as the error code caused by the disconnection
(SP.SOCCLOSE) instruction.
FX5U CPU, FX5UC CPU
GX Works3 Version 1.030G or later
0H
0H
Error
0H
code
Action
Refer to the MELSEC iQ-F FX5 User's Manual (Ethernet
Communication)