Technical Data - ABB Relion 611 series REB611 Product Manual

Busbar and multipurpose differential protection and control
Table of Contents

Advertisement

ABB
Busbar and Multipurpose Differential Protection and Control
REB611
Product version: 1.0

16. Technical data

Table 6. Dimensions
Description
Width
Height
Depth
Weight
Table 7. Power supply
Description
U
nominal
aux
Maximum interruption time in the
auxiliary DC voltage without
resetting the IED
U
variation
aux
Start-up threshold
Burden of auxiliary voltage supply
under quiescent (P
)/ operating
q
condition
Ripple in the DC auxiliary voltage
Fuse type
Table 8. Energizing inputs
Description
Rated frequency
Current inputs
Rated current, I
Thermal withstand capability:
• Continuously
• For 1 s
Dynamic current withstand:
• Half-wave value
Input impedance
1)
Ordering option for residual current input
2)
Residual current and/or phase current
Value
Frame
Case
Frame
Case
Complete IED
Plug-in unit only
Type 1
100, 110, 120, 220, 240 V AC
50 and 60 Hz
48, 60, 110, 125, 220, 250 V DC
50 ms at U
rated
n
38...110% of U
(38...264 V AC)
n
80...120% of U
(38.4...300 V DC)
n
DC < 12.0 W (nominal)/< 18.0 W (max.)
AC < 16.0 W (nominal)/< 21.0 W (max.)
Maximum 15% of the DC value (at frequency of 100 Hz)
T4A/250 V
Value
50/60 Hz
1)
0.2/1 A
n
4 A
100 A
250 A
< 100 mΩ
1MRS757467 B
177 mm
164 mm
177 mm (4U)
160 mm
201 mm (153 + 48 mm)
4.1 kg
2.1 kg
Type 2
24, 30, 48, 60 V DC
50...120% of U
(12...72 V DC)
n
19.2 V DC (24 V DC * 80%)
DC < 12.0 W (nominal)/< 18.0 W (max.)
2)
1/5 A
20 A
500 A
1250 A
< 20 mΩ
13

Hide quick links:

Advertisement

Table of Contents
loading