ABB
Busbar and Multipurpose Differential Protection and Control
REB611
Product version: 1.0
Table 20. Electromagnetic compatibility tests
Description
1 MHz/100 kHz burst disturbance
test:
• Common mode
• Differential mode
3/10/30 MHz burst disturbance test:
• Common mode
Electrostatic discharge test:
• Contact discharge
• Air discharge
Radio frequency interference tests:
Fast transient disturbance tests:
• All ports
Surge immunity test:
• Communication
• Other ports
Power frequency (50 Hz) magnetic
field:
• Continuous
• 1...3 s
Pulse magnetic field immunity test
Damped oscillatory magnetic field
immunity test
Voltage dips and short interruptions
Type test value
2.5 kV
2.5 kV
2 kV
8 kV
15 kV
10 V (rms)
f=150 kHz...80 MHz
10 V/m (rms)
f=80...2700 MHz
10 V/m
f=900 MHz
20 V/m (rms)
f=80...1000 MHz
4 kV
2 kV, line-to-earth
4 kV, line-to-earth
2 kV, line-to-line
300 A/m
1000 A/m
1000 A/m
100 A/m
30%/10 ms
60%/100 ms
60%/1000 ms
> 95%/5000 ms
1MRS757467 B
Reference
IEC 61000-4-18
IEC 60255-22-1, class III
IEEE C37.90.1-2002
IEC 61000-4-18
IEC 61000-4-2
IEC 60255-22-2
IEEE C37.90.3-2001
IEC 61000-4-6
IEC 60255-22-6, class III
IEC 61000-4-3
IEC 60255-22-3, class III
ENV 50204
IEC 60255-22-3, class III
IEEE C37.90.2-2004
IEC 61000-4-4
IEC 60255-22-4
IEEE C37.90.1-2002
IEC 61000-4-5
IEC 60255-22-5
IEC 61000-4-8
IEC 61000-4-9
IEC 61000-4-10
IEC 61000-4-11
17