ABB Relion 611 series REB611 Product Manual page 17

Busbar and multipurpose differential protection and control
Table of Contents

Advertisement

ABB
Busbar and Multipurpose Differential Protection and Control
REB611
Product version: 1.0
Table 20. Electromagnetic compatibility tests
Description
1 MHz/100 kHz burst disturbance
test:
• Common mode
• Differential mode
3/10/30 MHz burst disturbance test:
• Common mode
Electrostatic discharge test:
• Contact discharge
• Air discharge
Radio frequency interference tests:
Fast transient disturbance tests:
• All ports
Surge immunity test:
• Communication
• Other ports
Power frequency (50 Hz) magnetic
field:
• Continuous
• 1...3 s
Pulse magnetic field immunity test
Damped oscillatory magnetic field
immunity test
Voltage dips and short interruptions
Type test value
2.5 kV
2.5 kV
2 kV
8 kV
15 kV
10 V (rms)
f=150 kHz...80 MHz
10 V/m (rms)
f=80...2700 MHz
10 V/m
f=900 MHz
20 V/m (rms)
f=80...1000 MHz
4 kV
2 kV, line-to-earth
4 kV, line-to-earth
2 kV, line-to-line
300 A/m
1000 A/m
1000 A/m
100 A/m
30%/10 ms
60%/100 ms
60%/1000 ms
> 95%/5000 ms
1MRS757467 B
Reference
IEC 61000-4-18
IEC 60255-22-1, class III
IEEE C37.90.1-2002
IEC 61000-4-18
IEC 61000-4-2
IEC 60255-22-2
IEEE C37.90.3-2001
IEC 61000-4-6
IEC 60255-22-6, class III
IEC 61000-4-3
IEC 60255-22-3, class III
ENV 50204
IEC 60255-22-3, class III
IEEE C37.90.2-2004
IEC 61000-4-4
IEC 60255-22-4
IEEE C37.90.1-2002
IEC 61000-4-5
IEC 60255-22-5
IEC 61000-4-8
IEC 61000-4-9
IEC 61000-4-10
IEC 61000-4-11