ABB Relion 611 series REB611 Product Manual page 14

Busbar and multipurpose differential protection and control
Table of Contents

Advertisement

Busbar and Multipurpose Differential Protection and Control
REB611
Product version: 1.0
Table 9. Binary inputs
Description
Operating range
Rated voltage
Current drain
Power consumption
Threshold voltage
Reaction time
Table 10. Signal output X100: SO1
Description
Rated voltage
Continuous contact carry
Make and carry for 3.0 s
Make and carry for 0.5 s
Breaking capacity when the control-circuit time
constant L/R<40 ms
Minimum contact load
Table 11. Signal outputs and IRF output
Description
Rated voltage
Continuous contact carry
Make and carry for 3.0 s
Make and carry 0.5 s
Breaking capacity when the control-circuit time
constant L/R<40 ms, at 48/110/220 V DC
Minimum contact load
14
Value
±20% of the rated voltage
24...250 V DC
1.6...1.9 mA
31.0...570.0 mW
18...176 V DC
3 ms
Value
250 V AC/DC
5 A
15 A
30 A
1 A/0.25 A/0.15 A
100 mA at 24 V AC/DC (2.4 VA)
Value
250 V AC/DC
5 A
10 A
15 A
1 A/0.25 A/0.15 A
100 mA at 24 V AC/DC (2.4 VA)
1MRS757467 B
ABB

Hide quick links:

Advertisement

Table of Contents
loading