Installer/Servicer Notes For The Use Of Gas Oil With Bio Blends Up To 10; Operating Position; Boiler Plate - Riello RLS 100 Installation, Use And Maintenance Instructions

Dual fuel gas oil/ gas burners
Table of Contents

Advertisement

5.4

Installer/Servicer notes for the use of Gas oil with Bio blends up to 10%

 During the burner installation, check that the gasoil and bio
fuel blends are in accordance with Riello specifications
(please refer to the chapters "Technical Data" and "Guid-
ance for the use of bio fuel blends up to 10%" within the
burner technical manual).
 If a Bio blend is in use the installer must seek information
from the end user that their fuel supplier can evidence that
the blends of fuel conform to the relevant standards.
 Check that the materials used in the construction of the oil
tank and ancillary equipment are suitable for bio fuels, If not
these must be upgraded or replaced with Bio compatible
parts.
 Particular attention should be given to the oil storage tank
and supply to the burner. Riello recommends that existing
oil storage tanks are cleaned, inspected and any traces of
water are removed BEFORE bio fuel is introduced (Contact
the tank manufacturer or oil supplier for further advice). If
these recommendations are not respected this will increase
the risk of contamination and possible equipment failure.
 In line oil filters should be replaced making sure that they
are Bio compatible. Riello recommends a good quality bio
5.5

Operating position

The burner is designed to work only in the positions 1, 2, 3 and 4.
Installation 1 is preferable, as it is the only one that allows per-
forming maintenance operations as described in this manual.
Installations 2, 3 and 4 permit operation but make maintenance
and inspection of the combustion head difficult, page 33.
1
S8255
5.6

Boiler plate

Drill the combustion chamber locking plate as shown in Fig. 8.
The position of the threaded holes can be marked using the ther-
mal screen supplied with the burner.
mm
RLS 70
185
RLS 100
195
RLS 130
195
2
A
B
275 - 325
275 - 325
275 - 325
Installation
compatible oil filter at the tank and a secondary 100 micron
filter are used to protect the burner pump and nozzle from
contamination.
 The burner hydraulic components and flexible oil lines must
be suitable for bio fuel use (check with Riello if in doubt).
Riello have carefully chosen the specification of the bio
compatible components including the flexible oil lines to
protect the pump, safety value and nozzle. The Riello war-
ranty is dependent upon the use of Riello genuine compo-
nents including the oil lines, being used. The burner must
be commissioned and combustion parameters set to appli-
ance manufacturer's recommendations.
 Regularly check visually for any signs of oil leakage from
seals, gaskets and hoses.
 It is strongly recommended that with Bio fuel use, oil filters
are inspected and replaced every 4 months. More regularly
where contamination is experienced.
 During extended periods of non operation and/or where
burners are using oil as a standby fuel, it is strongly recom-
mended that the burner is put into operation for shorts peri-
ods at least every three months.
WARNING
3
C
M 12
M 12
M 12
Tab. G
15
GB
Any other position could compromise the correct
working of the appliance.
Installation 5 is prohibited for safety reasons.
4
5
Fig. 7
D455
Fig. 8
20033295

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rls 70Rls 130

Table of Contents