5. operation

fig.4
function setting
5.1.
this air conditioner has 3 functions: cooling, dehumidifying and fan.
control keys
5.2.
power key: press to turn on/off.
mode key: sets cooling, dehumidifying and fan modes.
fan speed: press to select high/low fan speed (not available in dehumidifying mode.)
timer key: when setting the time the regular time indicator will light.
up/down key: press these buttons to set the desired room temperature and time.
switch between °c and °f by pressing these two keys simultaneously or by using the remote control.
5.3.
operation
cooling mode:
5.3.1.
Ta≥Ts +1°C (1°F), the cooling will start.
Ta≤Ts -1°C (1°F), the compressor stops and only the fan motor remains working at the set fan speed.
ta: room surrounding temperature
ts: setting temperature
in this mode, press timer and down button to set sleep function, in sleep function, after operating two hours, the set temperature
increases 1°c (1°f) automatically.
After operating for another 2 hours, the set temperature will increase 1°c (1°f) again. then the set temperature will not change and
the fan will switch to low level.
dehumidifying mode:
5.3.2.
If the ambient temperature ≥17°C (62°F), the compressor will start. Then, the unit is controlled in the following manner:
When the ambient temperature ≤15°C (59°F), the compressor shuts down.
When the ambient temperature rises to be ≥17°C (62°F), the compressor starts again. The start/stop of the compressor meets the
requirement for 3-minute protection time.
5.3.3.
fan mode:
Fan runs on both high speed or low speed. Temperature setting displays environment temperature between 0 / 35°C (50 / 95°F).