Danfoss FCM 300 Series Design Manual page 69

Hide thumbs Also See for FCM 300 Series:
Table of Contents

Advertisement

Description of choice:
States in Hex format whether there is a warning on
the FC motor.
Hex
Status messages
01
Ramping
04
Start clockwise/counterclockwise
08
Slow down
10
Catch-up
8000
Frequency limit
542 Data read-out: Terminal 1, analogue input
(ANALOG INPUT 1)
Value:
Unit: mA
Function:
This parameter can be read out via the serial
communication port.
Description of choice:
The value shown indicates the signal value on
terminal 1.
The scaling (parameters 336 and 337) does not
influence the read-out. Min. and max. are determined
by the offset and gain adjustment of the AD-
converter.
This value is updated every 20 ms.
543 Data read-out: Terminal 2, analogue input
(ANALOG INPUT 2)
Value:
Unit: X.X V
Function:
This parameter can be read out via the serial
communication port.
Description of choice:
The value shown indicates the signal value on
terminal 2.
The scaling (parameters 338 and 339) does not
influence the read-out. Min. and max. are determined
by the offset and gain adjustment of the AD-
converter.
This value is updated every 20 ms.
= factory setting. ( ) = parameter window text. [ ] = value for use in communication via serial communication port
MG.03.B6.02 - VLT is a registered Danfoss trademark
FCM 300 Series
600 Operating data: Operating hours
(OPERATING HOURS)
Value:
Unit: hours
0.0 - 130,000.0
Function:
This parameter can be read out via the display or the
serial communication port. The value cannot be reset.
Description of choice:
Indicates the number of hours in which the FC motor
has been switched on.
The value is updated in the FC motor every hour and
saved when the unit is turned off.
601 Operating data: Hours run
(RUNNING HOURS)
Value:
Unit: hours
0.0 - 130,000.0
Function:
This parameter can be read out via the display or the
serial communication port. The value can be reset via
parameter 619.
Description of choice:
Indicates the number of hours in which the FC motor
has been in operation since reset in parameter 619.
The value is updated in the FC motor every hour and
saved when the unit is turned off.
603 Operating data: Number of power-up's
(POWER UP'S)
Value:
Unit: number
0 - 9999
Function:
This parameter can be read out via the display or the
serial communication port.
Description of choice:
States the number of power-ups of the supply voltage
to the FC motor.
69