Appendix:

Appendix 1: Reference Sheet of Celsius and Fahrenheit

Conversion formula for Fahrenheit degree and Celsius degree: Tf=Tcx1.8+32
Set temperature
Fahrenheit
display
Fahrenheit
temperature
(℉)
61
62/63
64/65
66/67
68
Ambient temperature
Fahrenheit
display
Fahrenheit
temperature
(℉)
32/33
34/35
36
37/38
39/40
41/42
43/44
45
46/47
48/49
50/51
52/53
54

Appendix 2: Configuration of Connection Pipe

1.Standard length of connection pipe
● 5m, 7.5m, 8m.
2.Min. length of connection pipe is 3m.
3.Max. length of connection pipe and max. high difference.
4.The additional refrigerant oil and refrigerant charging required after
prolonging connection pipe
● After the length of connection pipe is prolonged for 10m at the basis
of standard length, you should add 5ml of refrigerant oil for each
additional 5m of connection pipe.
● The calculation method of additional refrigerant charging amount (on
the basis of liquid pipe):
● When the length of connection pipe is above 5m, add refrigerant according to the prolonged length of liquid pipe. The additional
refrigerant charging amount per meter is different according to the diameter of liquid pipe. See the following sheet.
● Additional refrigerant charging amount = prolonged length of liquid pipe X additional refrigerant charging amount per meter
Installation and Maintenance
Fahrenheit
Celsius (℃)
temperature
(℉)
60.8
16
62.6
17
64.4
18
66.2
19
68
20
Fahrenheit
Celsius ( ℃)
temperature
(℉)
32
0
33.8
1
35.6
2
37.4
3
39.2
4
41
5
42.8
6
44.6
7
46.4
8
48.2
9
50
10
51.8
11
53.6
12
Additional refrigerant charging amount for R22, R407C, R410A and R134a
Diameter of connection pipe
Liquid pipe(mm)
Gas pipe(mm)
Ф6
Ф9.5 or Ф12
Ф6 or Ф9.5
Ф16 or Ф19
Ф12
Ф19 or Ф22.2
Ф16
Ф25.4 or Ф31.8
Ф19
Ф22.2
display
Fahrenheit
Celsius (℃)
(℉)
(℉)
69/70
69.8
71/72
71.6
73/74
73.4
75/76
75.2
77
77
display
Fahrenheit
Celsius(℃)
(℉)
(℉)
55/56
55.4
57/58
57.2
59/60
59
61/62
60.8
63
62.6
64/65
64.4
66/67
66.2
68/69
68
70/71
69.8
72
71.6
73/74
73.4
75/76
75.2
77/78
77
5000 Btu/h(1465 W)
7000 Btu/h(2051 W)
9000 Btu/h(2637 W)
12000 Btu/h(3516 W)
18000 Btu/h(5274 W)
24000 Btu/h(7032 W)
28000 Btu/h(8204 W)
36000 Btu/h(10548 W)
42000 Btu/h(12306 W)
48000 Btu/h(14064 W)
Outdoor unit throttle
Cooling only(g/m)
15
15
30
60
/
250
/
350
Fahrenheit
display
Fahrenheit
temperature
(℉)
21
78/79
22
80/81
23
82/83
24
84/85
25
86
Fahrenheit
display
Fahrenheit
temperature
(℉)
13
79/80
14
81
15
82/83
16
84/85
17
86/87
18
88/89
19
90
20
91/92
21
93/94
22
95/96
23
97/98
24
99
25
Max length of
Cooling capacity
connection pipe
15 m
15 m
15 m
20 m
25 m
25 m
30 m
30 m
30 m
30 m
Cooling and heating(g/m)
20
20
120
120
250
350
Celsius (℃)
(℉)
78.8
26
80.6
27
82.4
28
84.2
29
86
30
Celsius (℃)
(℉)
78.8
26
80.6
27
82.4
28
84.2
29
86
30
87.8
31
89.6
32
91.4
33
93.2
34
95
35
96.8
36
98.6
37
Max height
difference
5 m
5 m
10 m
10 m
10 m
10 m
10 m
20 m
20 m
20 m
57