Info; Mbus; Default Communication Settings; Transferred Values - Beko METPOINT Installation And Operating Manual

Thermal flow meter
Table of Contents

Advertisement

Installation and operating manual
Setup → 4 - 20 mA → Error Current

6.9. Info

Setup → Info

6.10. MBus

6.10.1. Default communication settings

Primary address*: 1
ID:
Serial number of sensor
Baud rate*:
2400
Medium*:
Gas

6.10.2. Transferred values

Value 1 with [Unit]*:
Value 2 with [Unit]*:
Value 3 with [Unit]*:
Value 4 with [Unit]*:
* these values can be factory-set or changed on request.
38
On this screen, you can enter the error signal to be sent by the analog output
in the event of a fault.
2 mA = sensor fault / system error
22 mA = sensor fault / system error
None = output according to Namur (3.8 mA ... 20.5 mA)
< 4mA to 3.8 mA = value below measuring range
> 20 mA to 20.5 mA = value above measuring range
Confirm your entry by pressing the >>ENTER<< button.
This screen shows device information.
Press "Details" to view the calibration conditions.
Flow [m³/h]
Consumption [m³]
Velocity [m/s]
Gas temperature [°C]
EN
METPOINT
SF53
®

Advertisement

Table of Contents
loading

Table of Contents