Fluke 1736 User Manual page 79

Power logger
Hide thumbs Also See for 1736:
Table of Contents

Advertisement

Power Quality Measurements
Measured Parameter .......................................... Voltage, Frequency, Unbalance, Voltage Harmonics, THD V, Current Harmonics, THD A, and TDD
Averaging Interval ............................................... 10 min
Individual Harmonics .......................................... 2
Total Harmonic Distortion ................................... Calculated on 50 harmonics
Events ................................................................. Voltage: Dips, Swells, Interruptions
Triggered Recordings ......................................... 1738 or 1736 with 1736/Upgrade license
Standards Compliance
Harmonics .......................................................... IEC 61000-4-7: Class 1
Power Quality ..................................................... IEC 61000-4-30 Class S, IEC62586-1 (PQI-S device)
Power ................................................................. IEEE 1459
Power Quality Compliance ................................. 1738 or 1736 with 1736/Upgrade license
Interfaces
USB-A ................................................................. File transfer via USB Flash Drive, Firmware updates, max. supply current: 120 mA
WiFi
Supported modes ........................................... Direct connection and connection to infrastructure (requires WiFi-Infrastructure license)
Security ........................................................... WPA2-AES with pre-shared key
Bluetooth ............................................................ read auxiliary measurement data from Fluke Connect 3000 series modules (requires WiFi/BLE adapter
USB-mini ............................................................ Data download device to PC
Extension port ..................................................... Accessories
(requires IEEE519/Report license)
nd
th
... 50
Current: Inrush Current
Half cycle RMS of Voltage and Current
Waveform of Voltage and Current
IEEE 519 (short time harmonics, requires IEEE519/Report license)
EN50160 (for measured parameters)
USB1 FC)
Power Logger
Electrical Specifications
69

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

1738

Table of Contents