13.2

Heat Exchanger (HEX) Protection Control

Start Condition:
- When outdoor ambient temperature is less than 10°C.
Control Details:
- Heater will turn ON and heat pump turn OFF when water inlet temperature below 10°C.
- Heater will turn OFF and heat pump turn ON when water inlet temperature increase more than 12°C.
End Condition:
- When outdoor ambient temperature is more than 13°C.
However this control will take place 29 minutes after compressor restart.
Water Inlet
(Compressor ON,
10°C
Deice (Compressor OFF,
Free Zone
Heater OFF)
Heater ON)