Protection Control for Cooling Operation

13.3.1 Outdoor Air Temperature Control
The Compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the
diagram below.
This control will begin 1 minute after the compressor starts.
Compressor frequency will adjust base on outdoor air temperature.
13.3.2 Freeze Prevention Control 1
1
When indoor heat exchanger temperature is lower than 0°C continuously for 10 seconds, compressor will
stop operating.
2
Compressor will resume its operation three minutes after the indoor heat exchanger is higher than 1°C.
3
Indoor heat exchanger freeze prevention (H99) will memory in error history.

13.4 Heat Exchanger (HEX) Protection Control

Start Condition:
When outdoor ambient temperature is less than 10°C
Control Details:
Heater will turn ON and heat pump turn OFF when water inlet temperature below 10°C.
Heater will turn OFF and heat pump turn ON when water inlet temperature increase more than 12°C
End Condition:
When outdoor ambient temperature is more than 13°C
However this control will take place 29 minutes after compressor restart.
Free
25°C
Limited
requency
Water Inlet
Free Zone
(Compressor ON, Heater OFF)
10°C
Deice (Compressor OFF,
Heater ON)
91
22°C
12°