Panasonic WH-MXC16G9E8 Service Manual page 113

Air-to-water heatpump system mono bloc unit
Hide thumbs Also See for WH-MXC16G9E8:
Table of Contents

Advertisement

16.5.21 Input Over Current Detection (F16)
Malfunction Decision Conditions:
During operation of cooling and heating, when outdoor current above 27.9A is detected by the current
transformer (CT) in the outdoor unit PCB.
Malfunction Caused:
1. Excessive refrigerant.
2. Faulty outdoor unit PCB (main).
Abnormality Judgment:
Continue 3 times in 20 minutes.
113