Wiring
3.1 Pin assignment
PROFINET interface X1 with 2-port switch (X1 P1 R and X1 P2 R)
The assignment corresponds to the Ethernet standard for an RJ45 plug.
● When autonegotiation is deactivated, the RJ45 socket is allocated as a switch (MDI-X).
● When autonegotiation is activated, autocrossing is in effect and the RJ45 socket is
allocated either as data terminal equipment (MDI) or a switch (MDI-X).
Figure 3-2
Reference
You can find additional information on the topics of "Connecting the CPU" and
"Accessories/spare parts" in the S7-1500, ET 200MP
(http://support.automation.siemens.com/WW/view/en/59191792) system manual.

Assignment of the MAC addresses

The CPU 1511T-1 PN has a PROFINET interface with two ports. The PROFINET interface
itself has a MAC address, and each of the two PROFINET ports has its own MAC address.
The CPU 1511T-1 PN therefore has three MAC addresses in total.
The MAC addresses of the PROFINET ports are needed for the LLDP protocol, for example
for the neighborhood discovery function.
The number range of the MAC addresses is sequential. The first and last MAC address are
lasered on the rating plate on the right side of each CPU 1511T-1 PN.
26

PROFINET ports

CPU 1511T-1 PN (6ES7511-1TK01-0AB0)
Manual, 09/2016, A5E36270833-AA