Ac Or Dc Power Supply Installation - Dell S6100 Installation Manual

On system
Hide thumbs Also See for S6100:
Table of Contents

Advertisement

1
PSU 1 and 2
The PSUs have an integrated fan, which you cannot replace individually; if the fan integrated in a PSU fails, you must replace the entire
PSU. You can replace the fan trays individually. For fan tray replacement procedures, see Fans.
WARNING:
Prevent exposure and contact with hazardous voltages. Do not attempt to operate this system with the safety cover
removed.
CAUTION:
Remove the power cable from the PSU before removing the PSU. Also, do not connect the power cable before you
insert the PSU in the chassis.
NOTE:
To comply with the GR-1089 Lightning Criteria for Equipment Interfacing with AC Power Ports, use an external surge
protection device (SPD) at the AC input of the router.

AC or DC power supply installation

NOTE:
The PSU slides into the slot smoothly. Do not force a PSU into a slot as this action may damage the PSU or the S6100–
ON chassis.
NOTE:
Ensure that you correctly install the PSU. When you install the PSU correctly, the power connector is on the right side of
the PSU.
1
Remove the PSU slot cover from the S6100-ON using a small #1 Phillips screwdriver.
2
Remove the PSU from the electro-static bag.
3
Use the grab handle and the orange tab to insert the PSU into the switch PSU slot.
Insert the PSU exposed PCB edge connector first. The PSU slot is keyed so that the PSU can only be fully inserted in one orientation.
34
Power supplies