Control Wiring - AB Quality PowerFlex 700S Quick Start Manual

Table of Contents

Advertisement

16
PowerFlex® 700S Drive
Table E Terminal Block Designations
Terminal
Description
BR1
DC Brake (+)
BR2
DC Brake (–)
DC+
DC Bus (+)
DC–
DC Bus (–)
PE
PE Ground
Motor Ground
U
U (T1)
V
V (T2)
W
W (T3)
R
R (L1)
S
S (L2)
T
T (L3)

Control Wiring

Important points to remember about I/O wiring:
• Always use copper wire.
• Wire with an insulation rating of 600V or greater is recommended.
• Control and signal wires should be separated from power wires by at
least 0.3 meters (1 foot).
Important: I/O terminals labeled "(–)" or "Common" are not referenced to
earth ground and are designed to greatly reduce common mode
interference. Grounding these terminals can cause signal noise.
Recommended Control Wire
Type
Wire Type(s)
Signal
Analog I/O Belden 8760/9460(or
equiv.)
Belden 8770(or equiv.)
Encoder/
Less than or equal to 30 m
Pulse I/O
(98 ft.) – Belden 9728 (or
equiv.)
Greater than 30 m (98 ft.) –
Belden 9773(or equiv.)
Digital I/O
Unshielded Per US NEC or applicable
national or local code
Shielded
Multi-conductor shielded
cable such as Belden
8770(or equiv.)
EMC
Refer to EMC Instructions for details.
Compliance
(1) If the wires are short and contained within a cabinet which has no sensitive circuits, the use of shielded wire
may not be necessary, but is always recommended.
Notes
Dynamic Brake Resistor Connection (+)
Dynamic Brake Resistor Connection (–)
DC Input Power or Dynamic Brake Chopper
DC Input Power or Dynamic Brake Chopper
Refer to
Figure 9 on page 14
for location on 3 Frame drives
Refer to
Figure 8 on page 13
for location on 3 Frame drives
To motor
To motor
To motor
AC Line Input Power
AC Line Input Power
AC Line Input Power
Description
2
0.750 mm
(18AWG),
twisted pair, 100% shield
(1)
with drain
.
2
0.750 mm
(18AWG), 3
cond., shielded for remote
pot only.
0.196 mm
2
(24AWG),
individually shielded.
2
0.750 mm
(18AWG),
twisted pair, shielded.
2
0.750 mm
(18AWG), 3
conductor, shielded.
Insulation
Rating
300V,
75-90° C
(167-194°
F), Minimum
300V,
60° C
(140° F),
Minimum

Advertisement

Table of Contents
loading

Related Products for AB Quality PowerFlex 700S

Table of Contents