Ethernet Configuration - ABB RET670 Operator's Manual

Transformer protection
Hide thumbs Also See for RET670:
Table of Contents

Advertisement

Section 9
Read and change settings
9.2.2.5
46
Main menu/Settings/General settings/Communication/Station communication/
MultiCommandSend/MULTICMDSND:x
Includes available instances of Multicommand send settings allowing the user to
adjust the maximum and minimum cycle time.
Multicommand receive
Main menu/Settings/General settings/Communication/Station communication/
MultiCommandReceive/MULTICMDRCV:x
Includes available instances of Multicommand receive settings allowing the user to
adjust the maximum and minimum cycle time, the pulse duration and mode of
operation. The mode of operation is either steady or pulsed.
Horizontal communication via GOOSE for interlocking
Main menu/Settings/General settings/Communication/Station communication/
ReceivingInterlInfo/GOOSEINTLKRCV:x
Includes available instances of GOOSEINTLKRCV for horizontal communication
via GOOSE. Each instance or set can be switched On or Off via the Operation On
and Off parameter.

Ethernet configuration

Main menu/Settings/General settings/Communication/Ethernet configuration/
Front port
The IP Address and IP mask for the ethernet port on the front panel of the IED are
set here. These are generally used when connecting a PC directly to the IED.
Remember that this is a static IP address and that the appropriate network settings
must also be made in the PC.
Main menu/Settings/General settings/Communication/Ethernet configuration/
Rear OEM-Port AB
The IP address, IP mask and Mode for the IEC 61850-8-1 communication using the
Optical Ethernet Module (OEM) at the rear of the IED are set here.
Main menu/Settings/General settings/Communication/Ethernet configuration/
Rear OEM-Port CD
The IP address (with different IP address when a second channel is used), IP mask
and Mode for the Optical Ethernet Module (OEM) at the rear of the IED are set
here. The CD port is used for IEC 61850-9-2LE communication.
Main menu/Settings/General settings/Communication/Ethernet configuration/
Rear OEM - Redundant PRP
Redundant station bus communication IEC61850-8-1 are set here.
1MRK504114-UEN E
Operator's manual