Test /Setting Modes
The following tests and settings can be changed while in test mode:
• Sensor Setting Mode including PIR or Audio Sensitivity, and Sensor
Occupancy Timer
• Walk-Test Mode
• LED indication selection
Sensor Setting Mode
This mode allows adjustment of the PIR Sensitivity, Audio Sensitivity and Sensor
Occupancy Timer duration. The faceplate must be removed to allow access to
the teach button.
NOTE: New settings do not take affect until you save and exit.
1. To enter sensor setting mode, press and hold the teach button until all the
LEDs blink simultaneously (about 5 seconds).
2. A quick press of the button at this level will allow you to scroll between the
test/setting modes. When the red and yellow LEDs are blinking, go to step 3.
3. Press and hold the button again until the LEDs stop blinking to select this
mode, about 5 seconds.
4. A quick press of the button at this level scrolls between:
5. Press and hold the teach button again for 5 seconds to select the desired
sensor setting. The corresponding LED will blink according to the current
setting. Press the button to scroll through the available settings.
PIR Sensitivity - green LED blinks indicate setting
Audio Sensitivity - amber LED blinks indicate setting (DT model only)
NOTE: If the Disabled setting is selected for Audio Gain, this disables the
audio input however the Sensor Occupancy Timer will remain active.
Sensor Occupancy Timer - red LED blinks indicate setting (DT model
only)
NOTE: If the Disabled setting is selected for the Sensor Occupancy Timer,
the audio will remain active the entire 60 minute duration of the Audio
6
Double Green - PIR Sensitivity
Double Amber - Audio Gain (DT model only)
Double Red - Occupancy Sensor Timer (DT model only)
1 blink = high (default)
2 blinks = medium
3 blinks = low
1 blink = automatic (default)
2 blinks = low sensitivity
3 blinks = disabled
1 blink = disabled
2 blinks = 5 minutes
3 blinks = 10 minutes
4 blinks = 15 minutes
5 blinks = 20 minutes (default)
6 blinks = 25 minutes