Eaton Cutler-Hammer IQ DP-4000 Installation, Operation And Maintenance Instructions page 43

Electrical distribution system monitor
Hide thumbs Also See for Cutler-Hammer IQ DP-4000:
Table of Contents

Advertisement

IQ DP-4000
SECTION 6 - TROU BLESHOOTING AND MAINTENANCE
Advanced Products Support Center {APSC) at
809-2772.
Symptom
All Operator Panel indicators are off.
Digit 1 flashes in the display window,
indicating an external trip.
Digit
2
flashes in the display window
indicating an overvoltage
Digit 3 flashes in the display window,
indicating an undervoltage.
Digit
flashes in the display window,
4
indicating a phase unbalance.
Digit 5 flashes in the display window,
indicating a voltage phase loss.
Digit 6 flashes in the display window,
indicating a cu rrent phase loss.
Digit
7
flashes
in
display
indicating a phase reversal.
8
Digit
flashes
i n
display
indicating an internal malfunction.
One
or
more
voltage
incorrectly.
Cu rrent readings are not accurate or read
zero.
Power readings are incorrect.
Table 6 . A Initial Power-On Troubleshooting
40
1 -800-
Probable Cause(s)
AC line voltage level is deficient.
Separate Source AC control power is
deficient (only if using separate source
power module).
AC line, o r optional, external PTs are not
properly selected, wired, or installed.
A
trip
condition
i nitiated
through
Port.
AC line, o r optional, external PTs are not
properly i n stalled or wired.
An Undervoltage condition actually exists.
A Phase Unbalance condition exists.
A Voltage Phase Loss condition exists.
Blown o r loose fuse(s).
A C u rrent Phase Loss condition exists.
window,
A Phase Reversal condition exists.
I Q
window,
DP-4000
malfunction.
phases
read
Blown or loose fuse(s).
I nco rrect PT ratio.
I ncorrect size CTs used.
I ncorrect CT ratio.
Phasing
incorrect.
has
been
externally
the
Communications
detecting
an
internal
is
for
voltage
and
cu rrent
Solution
Locate cause of deficiency in AC line
monitored.
Locate the cause of the deficiency in the
AC
control
power
line.
sufficient, replace unit.
Verify that the AC line and/or PTs are
wired
as
shown
on
drawings for the application.
Determine why the trip was i nitiated from
the
external
device
Communications Option.
Verify that the AC line, and PTs are
installed and wired as shown on the
wiring plan drawi ng for the application.
Isolate the AC line deficiency's cause.
Isolate
the
cause
of
deficiency.
Isolate the cause of the
cause.
on
Check
the
fuse(s)
phase(s).
Reseat
fuse(s).
necessary.
Correct the i mproper wiring.
Isolate the cause of the AC line reversal.
Check the utility to determine thei r phase
sequence.
Replace the unit.
Check fuse(s) on the affected phase(s).
Reseat the fuse(s). Replace if necessary.
Check PT ratio.
Replace with proper size CTs.
Check CT ratio.
is
Check phasing. Verify connections with
wiring diagrams.
TD1 7548A
If
power
is
the
wiring
plan
through
the
the
AC
line
AC line phase
the
affected
Replace
if