The first 30 minutes of cooling operation, (A) will be applied.

13.12 IPM (power transistor) Protection Control

Overheating Prevention Control
If IPM temperature rises to 176°F (80°C), outdoor fan speed will be increased.
o
When the IPM temperature rises to 203°F (95°C), compressor operation will stop immediately.
o
Compressor operation restarts when temperature decreases to 194°F (90°C).
o
If IPM temperature detected less than -22°F (-30°C), IPM is judged as open circuit ("F96" is indicated).
o
DC peak current control
When IPMDC current exceeds set value of 30.0 ± 3.0 A, the compressor will stop.
o
If the DC peak current detected within 30 seconds after operation starts, compressor will restart after
o
1 minute.
If the DC peak current detected 30 seconds or more after operation starts, compressor will restart after
o
2 minutes.
Within 30 seconds after compressor restarts, if the DC peak current is exceeded set value continuously for
o
7 times, all indoor and outdoor relays will be cut off ("F99" is indicated).
Error reset can be done by power supply reset.

13.13 Compressor Protection Control (Gas leak detection control 1)

Control start conditions
For 5 minutes, the compressor continuously operates and total current is low.
o
During Cooling or Soft Dry operation:
o
Indoor intake temperature — indoor piping temperature is below 39.2°F (4°C).
During Heating operation:
o
Indoor pipe temperature — indoor intake temperature is below 37.4°F (3°C).
Not during deice control.
o
Compressor ON with maximum frequency.
o
Control content
Compressor stops (and restart after 3 minutes)
o
If the conditions above happen 4 times within 60 minutes, the unit will stop operation ("F91" is indicated).
o

13.14 Compressor Protection Control (Gas leak detection control 2)

This control detect gas leakage condition to prevent compressor damage.
Control start condition
All connected indoor units capability supply ON.
o
Compressor ON with maximum frequency.
o
Not during annual cooling.
o
Compressor discharge temperature high.
o
Control content
Compressor OFF during this control ("F91" is memorized in EEPROM)
o
If the above conditions happen 2 times within 60 minutes, indoor units' Timer LED will blinks ("F91" is
o
indicated at all indoor units)
102.2°F (39°C)
Outdoor air temperature
(B)
(A)
100.4°F (38°C)