13.5 Cooling overload control (Cool)

This control detect outdoor pipe temperature and perform the compressor frequency restriction during cooling
operation.
The compressor will be stopped to avoid compressor overloading.

13.6 Heating overload control (Heat)

This control detect indoor pipe temperature and perform the compressor frequency restriction during heating
operation.
This control detect outdoor ambient temperature and perform the fan speed adjustment during heating operation.
The compressor will be stopped to avoid compressor overloading.
Comp stop
147.2°F (64°C)
Comp freq
restricted
140°F (60°C)
Comp freq
free
OD Pipe
temp
COMP. ON
14.0°F (-10.0°C)
COMP. OFF
Outdoor
Air Temperature
140.0°F (60°C)
127.4°F (53°C)
118.4°F (48°C)
ID Pipe
temp
RPM controlled
53.6°F (12°C)
RPM free
OD temp
COMP. ON
-5.8°F (-21°C)
COMP. OFF
Outdoor
Air Temperature
55
134.6°F (57°C)
10.4°F (-12.0°C)
Comp stop
Comp freq
restricted
Comp freq
maintain
Comp freq
free
50.0°F (10°C)
-7.6°F (-22°C)