Binary Inputs And Outputs; Bim - Binary Input Module; Bim - Binary Input Module With Enhanced Pulse Counting Capabilities - ABB RED670 Product Manual

Line differential protection red670 2.1 iec
Hide thumbs Also See for RED670:
Table of Contents

Advertisement

Line differential protection RED670 2.1 IEC
Product version: 2.1

Binary inputs and outputs

Table 12. BIM - Binary input module
Quantity
Binary inputs
DC voltage, RL
Power consumption
24/30 V, 50mA
48/60 V, 50mA
110/125 V, 50mA
220/250 V, 50mA
220/250 V, 110mA
Counter input frequency
Oscillating signal discriminator
Debounce filter
Maximum 176 binary input channels may be
activated simultaneously with influencing
factors within nominal range.
Table 13. BIM - Binary input module with enhanced pulse counting capabilities
Quantity
Binary inputs
DC voltage, RL
Power consumption
24/30 V
48/60 V
110/125 V
220/250 V
Counter input frequency
Balanced counter input frequency
Oscillating signal discriminator
Debounce filter
Maximum 176 binary input channels may be
activated simultaneously with influencing
factors within nominal range.
ABB
Rated value
16
24/30 V
48/60 V
110/125 V
220/250 V
max. 0.05 W/input
max. 0.1 W/input
max. 0.2 W/input
max. 0.4 W/input
max. 0.5 W/input
10 pulses/s max
Blocking settable 1–40 Hz
Release settable 1–30 Hz
Settable 1–20ms
Rated value
16
24/30 V
48/60 V
110/125 V
220/250 V
max. 0.05 W/input
max. 0.1 W/input
max. 0.2 W/input
max. 0.4 W/input
10 pulses/s max
40 pulses/s max
Blocking settable 1–40 Hz
Release settable 1–30 Hz
Settable 1-20 ms
1MRK 505 346-BEN -
Nominal range
-
RL ±20%
RL ±20%
RL ±20%
RL ±20%
-
-
Nominal range
-
RL ±20%
RL ±20%
RL ±20%
RL ±20%
-
-
-
49

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rel670 2.1 iec

Table of Contents