Line differential protection RED670 2.1 IEC
Product version: 2.1
Table 60. Broken conductor check BRCPTOC
Function
Minimum phase current for operation
Unbalance current operation
Independent operate time delay
Independent reset time delay
Start time at current change from I
Reset time at current change from 0 to I
74
Range or value
(5–100)% of
IBase
(50–90)% of maximum current
(0.000-60.000) s
(0.010-60.000) s
to 0
Min. = 25 ms
r
Max. = 35 ms
Min. = 5 ms
r
Max. = 20 ms
Accuracy
±1.0% of I
r
±1.0% of I
r
±0.2% or ±45 ms whichever is greater
±0.2% or ±30 ms whichever is greater
-
-
1MRK 505 346-BEN -