Description
445
Information on country set-
up faulty
448
Neutral conductor error
451
Memory error for a micro-
controller
452
Communication between
filter and power module not
possible
453
Redundant grid monitoring
has detected faulty grid
voltage
454
Redundant grid monitoring
has detected faulty grid fre-
quency
456
Error detected in islanding
monitoring
457
Grid relay does not trigger
Behavior
1. Country setup information
faulty
2. Software old (e.g., after PC
board replacement)
3. Manual configuration in ser-
vice menu not possible
4. Recerbo faulty
1. No neutral conductor found
2. Incorrect setup
3. Bad contact: wall bracket <-
-> inverter
4. Filter PC board faulty
1. Grid problem
2. Faulty AC guard on filter PC
board
3. Faulty AC guard on power
module
1. Communication problem
caused by temporary environ-
mental faults (grid, EMC, etc.)
2. Check ribbon cable between
filter PC board and power mod-
ule
3. Filter PC board faulty
4. Power module faulty
1. Measurement error
2. Grid problem
3. Faulty AC guard on filter PC
board
4. Faulty AC guard on power
module
1. Measurement error
2. Grid problem
3. Faulty AC guard on filter PC
board
4. Faulty AC guard on power
module
1. Occurs once
2. Software problem
3. Measurement error on filter
PC board
4. Measurement circuit for anti-
islanding faulty
1. Occurs once
2. Grid test time is too low
3. Grid relay sticks
Remedy
1. Update software and reload
country setup from setup menu
2. Update software and reload
country setup from setup menu
3. Check settings
4. Replace Recerbo
1. Check cabling
2. Check country setup
3. Check fixing screws in DAT-
COM area
4. Replace filter PC board
1. Automatically corrected
2. Replace filter PC board
3. Replace power module
1. Automatically corrected
2. Replace ribbon cable
3. Replace filter PC board
4. Replace power module
1. Software update
2. Automatically corrected
3. Replace filter PC board
4. Replace power module
1. Software update
2. Automatically corrected
3. Replace filter PC board
4. Replace power module
1. Restart inverter
2. Software update
2. Replace filter PC board
3. Replace power module
1. Restart inverter
2. Change settings
3. Replace power module