Installing the device in the rack

About this task
Use the following procedure to install the device in the rack.
Procedure
1. Ensure that the door, if installed, is removed from the port side of the device.
2. Use a lift to raise the device to the level of the shelf brackets.
3. Move the lift as close as possible to the rack, with the air-intake side of the
4. If applicable, lock the wheels of the lift.
5. Gently slide the device onto the shelf brackets, ensuring that it remains
6. Fasten the port side of the device to the rack rails. Use three 10-32 x 5/8 inch
26
SAN512B-6 Installation, Service, and User Guide
device to the rack rails with 10-32 x 5/8 inch screws. Use three clips on each
rail. Place the clips in optimum locations for securing the device to the rails.
Note: Do not align the clip or retainer nuts with the top or bottom holes of the
mounting bracket because the screw heads will interfere with the door.
DANGER
Use safe lifting practices when moving the product.
18-32 kg (39.7-70.5 lbs)
For instructions, refer to instructions for removing and replacing the device
door in the device installation guide.
device facing the front of the rack (see the following figure).
supported during the transfer.
(1.58 cm) screws per rail. Tighten the screws to a torque of 32 in-lb (37 cm-kg).
Refer to Figure 5.
Note: Do not use the top or bottom holes of the mounting bracket because the
screw heads will interfere with the door.