CO2 sensor installation
IMPORTANT Do not install ZS CO
maintain accuracy, it must be installed only in a zone that is unoccupied for at least 4 hours a day with enough air
movement during the unoccupied period to return CO
A ZS sensor with CO
that deviates no more than 40PPM for at least 15 minutes, and assigns that value to the 400PPM baseline. This
daily Automatic Background Calibration may take up to 21 days to fully calibrate the sensor.
NOTE Dropping a sensor can upset the calibration, and it may require 21 days to return to our stated accuracy.
Motion sensor installation
The motion sensor on a ZS Pro needs to have a direct line of sight to the occupants in the room.
If the size of the room exceeds the maximum detector range, use multiple sensors to adequately monitor the area.
Avoid placing the sensor:
•
In a location that has a direct line of sight through an open door to a hallway where the sensor could detect
movement of people in the hallway.
•
Near air ducts. Rapidly changing air currents from the air ducts could lead to false sensor readings.
ZS Sensors
Installation Guide
Temperature sensor
or temperature with
humidity sensor
Sensor with CO
or VOC
2
FCC Part 15-Subpart B-Class B, CE
sensors in continuous occupancy applications. For a ZS CO
2
uses Automatic Background Calibration which waits for the lowest value in a 24-hour period
2
Carrier Proprietary and Confidential
Width:
3 in. (7.62 cm)
Height:
4-13/16 in. (12.22 cm)
13/16 in. (2.01 cm)
Depth:
Width:
2-7/8 in. (7.3 cm)
Height:
4-13/16 in. (12.22 cm)
Depth:
1-1/4 in. (3.18 cm)
to background levels.
2
11
ZS zone sensors
sensor to
2
CARRIER CORPORATION ©2017
All rights reserved