5.3
The maximum permitted speed can be limited by the parameters
480,
For this, the parameter
tion mode 110.
If the additional limitation has been activated, the maximum frequency (maybe per-
mitted by the load detection or its modification during the movement of a luffing jib) is
limited to the current fixed frequency. The limitation is effective for both clockwise
and anti-clockwise.
5.4
The properties of the asynchronous machine change with the temperature and can be
taken into account via a suitable measurement or estimate. Various methods and
sources of actual values for temperature detection are to be selected via the parame-
ter
The parameter
tion mode 4-temperature estimate in the configurations 260 and 460. In switching on,
the temperature of the asynchronous machine is estimated and taken into account for
correct calculation.
If this is not required, the parameter
must be parameterized to the operation mode 0-Off.
11 to 13
The
tion of the extended machine data has been carried out. The temperature can be read
out via the actual value parameter
optimization for the parameter.
06/05
06/05
Limitation of the speed by fixed frequencies
Fixed Frequency 2
Operation mode
0 -Off
110 -Fixed limit
Temperature adjustment
Operation mode Temperature adjustment
Operation mode Temperature adjustment
Operation mode
0 -Off
1 -Temp. Detect. At AE1
2 -Temp. Detect. At AE2
3 -Temp. Detect. At AE3
4 -Temperature estimate
Adjusting temperature
Parameter
No.
Description
467 Adjusting temperature
Fixed Frequency 3
481 ,
Frequency upper limit source
There is no additional speed limitation
The selected fixed frequencies are taken into ac-
count for limitation
465.
Operation mode Temperature adjustment
The function is deactivated
Temperature synchronization (0 ... 200
10V), actual temperature value to multifunctional input
1
Temperature synchronization (0 ... 200
10V), actual temperature value to multifunctional input
2
Temperature synchronization (0 ... 200
10V), actual temperature value to multifunctional input
3
Temperature synchronization by estimation
Operation modes 1 to 3 with the VECTRON extension
temperature synchronization (-26.0 ... 207.8
10V)
467 is to be set to the temperature at which the optimiza-
Winding temperature
Fixed Frequency 1
Fixed Frequency 3
482 and
769 is to be set to the opera-
Function
465 is pre-set to the opera-
Function
226 and can be used in the
Setting
Min.
Max.
-50.0 °C
300.0 °C
483.
465
°
C => 0/2 ...
°
C => 0/2 ...
°
C => 0/2 ...
°
C => 0 ...
Fact. sett.
100.0 °C
25
25