Cisco UCS 5108 Installation Manual page 102

Chassis
Hide thumbs Also See for UCS 5108:
Table of Contents

Advertisement

Specifications for the Cisco UCS 5108 Blade Server Chassis Power Supply Units
Item
DC input terminal block
Maximum holdup time
Table 22: HVDC-Input Platinum Power Supply (UCSB-PSU-2500HVDC) Specifications
Item
DC-input voltage
Maximum DC-input current
Maximum output power
Maximum inrush current
Efficiency rating
Efficiency (80 Plus Platinum Certified)
Power supply output voltage
Maximum holdup time
Input connector
Table 23: AC-input Dual Voltage Platinum Power Supply (UCSB-PSU-2500ACDV) Specifications
Description
AC-input voltage
AC-input frequency
AC-input current
Cisco UCS 5108 Server Chassis Installation Guide
90
Specification
Accepts Panduit LCD4-14AF-L or equivalent
barrel-type lug terminals with 90-degree angle, two-
hole tongue, which accommodates 1/0 AWG size
copper wire. The connector tongue width is 0.82 in,
the stud hole spacing is 5/8 in, and the hole size is 1/4
in.
8 ms at 50% load
4 ms at 100% load
Specification
200 to 380 VDC nominal (Range: 180 to 400 VDC)
15.5 Amps @ 200 VDC
2500 W
35 A
Climate Savers Platinum
10% 20% 50% 100%
93.5% 94.9% 95% 93%
12 VDC
12 ms 2500 W
IEC320 C20
Specification
200 to 240 VAC nominal (Range: 180 to 264 VAC)
100 to 120 VAC nominal (Range: 90 to 127 VAC)
supported only with the UCS 6324 Fabric Interconnect
50 and 60 Hz nominal (Range: 47 to 63 Hz)
< 15 Amps @ 200 VAC
Technical Specifications