Figure 13 Commissioning mode diagram
Display Sleep Mode
Any Key
No Operation
for 60sec.
Clock Display Mode
Enter
No Operation
for 60sec.
Clock Setting Mode
Heat Setting
Enter into Commissioning Mode
First option is the Heat Setting – Press Enter one more time to access this
Use UP/DOWN arrow keys to toggle between Heat On and Heat Off
Press Enter to confirm choice
To bypass the Heat Setting simply press the UP key to access the next parameter in the
Commissioning menu

Temperature Setting

Enter into Commissioning Mode
First option is the Heat Setting –
Press the UP Key to access Temperature Setting then Press Enter to access
Use UP/DOWN arrow keys to toggle between the various Temperature Settings
Press Enter to confirm choice
Settings available 130, 140, 150, 160, 165, 175°F
To bypass the Temperature setting simply press the UP key to access the next parameter
in the Commissioning menu
Hold down " UP " and
" DOWN " together
Press and
hold down Enter
or
Enter
No Operation
or
for 60sec.
Sanden Heat Pump – Installation Manual 
" DOWN " is reverse
Heat Setting Mode
UP
Outlet water Temp Setting Mode
UP
Block out Time Setting Mode
UP
Error History Display Mode
UP
Parameter Display Mode
Page 20 of 36 
Enter
Enter
Enter
UP
Enter
Enter