Sanden GS3-45HPA-US Installation Manual page 25

Heat pump water heater with natural refrigerant
Hide thumbs Also See for GS3-45HPA-US:
Table of Contents

Advertisement

High ambient temperature defrost
E008
drive error
E009
HP defrost thermistor detection error
HP inlet temperature thermistor wire
E011
break
HP outlet temperature thermistor wire
E012
break
HP discharge temperature thermistor
E013
wire break
HP defrost temperature thermistor
E014
wire break
HP ambient temperature thermistor
E015
wire break
E016
Tank thermistor wire break
HP inlet temperature thermistor wire
E021
short circuit
HP outlet temperature thermistor wire
E022
short circuit
HP discharge temperature thermistor
E023
wire short circuit
HP defrost temperature thermistor
E024
wire short circuit
HP ambient temperature thermistor
E025
wire short circuit
E026
Tank thermistor short circuit
E031
Fan motor locked
E032
Fan motor revolution error
E034
Water circulation pump locked
E040
System control error
E082
working, replace the pump
- In areas with hard water ensure Gas Cooler
is not scaled up, descale if necessary
- Remove debris from the evaporator coil
(e.g. leaves, grass, snow)
- Replace the ambient temperature thermistor
- Replace the defrost thermistor
- Check if the thermistor is mounted
in position on the evaporator
- Replace the defrost thermistor
- Check the thermistor connectors on the
main PCB in the heat pump unit for any
disconnect, wire breakage or short circuit
- Measure resistance of the specific
thermistor indicated by the error code
- Reconnect the connector, check if it is off
the PCB
- Ensure Fan Blade is not caught on debris or
snow/ice build-up inside the unit
- Replace the fan motor
- Check the heat pump piping for blockage or
kinking
- Confirm that the connector for the water
circulation pump is connected to the PCB
correctly
- Replace the water circulation pump
- In areas with hard water ensure piping is not
scaled up, descale if necessary
Replace the PCB
(In the case of E080, check the heat pump
piping for blockage/debris, any piping bend,
blockage or kinking and pipes are not frozen )
Sanden Heat Pump – Installation Manual 
Page 25 of 36 

Hide quick links:

Advertisement

Table of Contents
loading