Toshiba MCY-MHP0404HS-E Service Manual page 156

Multi type
Table of Contents

Advertisement

Step Component
4
Reactor
replacement
1. Detachment
AMP Air Conditioning
Procedure
WARNING
Do not detach the inverter for 5 minutes after
turning off the breaker as doing so may cause
electric shocks.
1) Remove the front panels, upper panel and
discharge cabinets. [Step.1 and Step.2]
2) Remove the screws of the inverter cover (B)
and reactor assembly.
(M4×10, 1 ) (Fig. 4-1)
3) Remove each wires of the reactor from reactor
terminal. (2 positions) (Fig. 4-2)
4) Disconnect the lead wires which are secured to
the clamp wire using the tie cable. (Fig. 4-2)
5) The reactor is lifted up and removed. (Fig. 4-3)
(Fig. 4-3)
(Fig. 4-1)
Clamp wire &
Reactor (CH-57-DN)
Banding band
155
www.ampair.co.uk | sales@ampair.co.uk
Remarks
Inverter cover (B)