Submerged Area Velocity Sensor Cable Quick-Connect; Desiccant Cartridge - Sigma 980 Operating And Maintenance Manual

Flowmeter
Table of Contents

Advertisement

Figure 27 Junction Box, Probe, Cable Connection, and Desiccant Canister

2.19.2 Submerged Area Velocity Sensor Cable Quick-Connect

2.19.2.1 Desiccant Cartridge

The quick-connect hub allows easy installation and removal of the submerged
area velocity sensor. Connect the submerged area velocity sensor cable to
the quick-connect hub:
1. Remove the rubber cap on the quick-connect hub. See
2. Place the connector-end of the cable to the quick-connect hub and tighten
the connection by turning the cable connector securement ring clockwise.
Make sure vinyl tubing is securely fastened at both fittings
to do so will allow fluid or moisture to pass down or block the pressure
transducers reference port. This will result in faulty readings and could lead to
sensor failure.
During installation, arrange the sensor so that the desiccant cartridge hangs
down as shown in the
Figure
27.
Wiring the Submerged Area Velocity Sensor
Section 2
Figure
25.
(Figure
27). Failure