Wiring The Rs232 - Sigma 980 Operating And Maintenance Manual

Flowmeter
Table of Contents

Advertisement

Section 2
2.13

Wiring the RS232

Note: Do not connect the RS232
port to more than one external
device at the same time. Connecting
an external device to both the side
panel quick-connect fitting and the
terminal circuit board inside the 980
Flow Meter can cause instrument
failure and unreliable
communications.
Note: To minimize electromagnetic
affects on the 980 Flow Meter
performance shielded cable is
required. To ensure that ground
currents in inadequate ground
systems do not result in potential
shock hazards do not connect the
shields at both ends of the cable.
Note: Route wires through
NEMA-approved conduit hubs
(Cat. No. 16483) to ensure
that water and dust do not enter the
enclosure.
Page 44
Wiring the RS232
The quick-connect RS-232 connector is located on the side panel of the
980 Flow Meter housing. The RS232 is intended for temporary connection
between a PC and 980 Flow Meter using a serial interface cable
(Cat. No. 1727) or a DTU-II. The 980 Flow Meter also allows for a permanent
connection that is routed by an external communications cable to the
980 Flow Meter through a conduit opening.
Permanent Conduit Connection
1. With power to the controller off, use a large flat-blade screwdriver to
loosen the two screws securing the 980 Flow Meter cover. Open the
cover. See
Wiring Safety Information on page
2. Disconnect the RS232 Quick-connect attached to the TB11 pins.
No wires should remain in the socket.
3. To prevent dangling wires from touching the circuit nodes, tape each
individual wire then bundle the wires and tape wires together.
See
Figure
19.
4. Attach a NEMA-approved conduit or compression fitting to one of the
½ in. openings on the bottom of the instrument, and route the RS232
permanent connection 6-wire cable and five conductors with shield.
5. Strip the outer insulated jacket back 2 inches from the end of the RS232
cable. Use care when removing the outer jacket to ensure that the
insulation around the inner conductors is not nicked. Nicked insulation on
inner conductors can lead to shorting.
6. Strip insulation of the individual wires back ¼ inch.
7. Connect each bare wire end to the proper screw terminal block (TB11).
Refer to
Table 9
and
Figure
exposed.
8. Connect the cable shield to protective earth (ground) at the 980 Flow
Meter. Do not connect the cable shield at the remote end of the cable. Cut
the cable jacket back far enough to expose the conductors and remove
the shield by cutting it even with the cable jacket. Insulate the remaining
exposed shield with tape or heat shrink tubing.
Table 9 Conduit RS232 Terminal Block Connections (TB11)
Pin
2
3
4
5
6
7
Reconnecting the RS232 Quick-Connect
1. With the power to the controller off, use a flat-blade screwdriver to loosen
the two screws securing the 980 Flow Meter cover.
31.
19. Do not leave any of the bare wire
Signal Description
TXD
DTR
RXD
DSR
common
shield

Hide quick links:

Advertisement

Table of Contents
loading

Related Products for Sigma 980

Table of Contents