LG Multi V 5 Data Manual page 24

Hide thumbs Also See for Multi V 5:
Table of Contents

Advertisement

COOLING CAPACITY DATA
ARUM144BTE5 / ARUM144DTE5
144,000 Btu/h 208-230V / 460V Outdoor Units
Outdoor
Combination
68/57
air temp.
(%)
TC
(°F DB)
MBh
-9.9
48.6
-5
48.6
0
48.6
5
48.6
10
48.6
14
48.6
20
48.6
25
48.6
30
48.6
35
48.6
40
48.6
45
48.6
50
48.6
55
48.6
50%
60
48.6
65
48.6
70
48.6
75
48.6
80
48.6
85
48.6
90
48.6
95
48.6
100
48.6
105
48.6
110
48.6
115
48.6
118
48.6
122
48.6
TC = Total Capacity (MBh).
PI = Power Input (kW) (includes compressor and outdoor fan).
Cooling range with the Low Ambient Baffle Kit (sold separately) is -9.9°F to +122°F and is achieved
only when all indoor units are operating in cooling mode. Does not impact heat recovery system
synchronous operating range.
The System Combination Ratio must be between 50–130%.
24 | PERFORMANCE DATA
73/61
79/64
PI
TC
PI
TC
kW
MBh
kW
MBh
1.16
57.9
1.36
67.5
1.22
57.9
1.43
67.5
1.27
57.9
1.49
67.5
1.31
57.9
1.55
67.5
1.35
57.9
1.59
67.5
1.40
57.9
1.65
67.5
1.45
57.9
1.70
67.5
1.50
57.9
1.74
67.5
1.54
57.9
1.79
67.5
1.58
57.9
1.83
67.5
1.62
57.9
1.88
67.5
1.65
57.9
1.91
67.5
1.67
57.9
1.93
67.5
1.70
57.9
1.97
67.5
1.74
57.9
2.02
67.5
1.76
57.9
2.06
67.5
1.81
57.9
2.09
67.5
1.83
57.9
2.13
67.5
1.88
57.9
2.25
67.5
2.01
57.9
2.38
67.5
2.24
57.9
2.66
67.5
2.36
57.9
2.82
67.5
2.48
57.9
2.98
67.5
2.72
57.9
3.29
67.5
3.00
57.9
3.64
67.5
3.21
57.9
3.90
67.5
3.47
57.9
4.24
67.5
3.83
57.9
4.68
67.5
©
Indoor Air Temp. °F DB/°F WB
80/67
85/70
PI
TC
PI
TC
kW
MBh
kW
MBh
1.52
72.0
1.64
76.5
1.61
72.0
1.73
76.5
1.67
72.0
1.80
76.5
1.73
72.0
1.87
76.5
1.78
72.0
1.92
76.5
1.85
72.0
1.99
76.5
1.92
72.0
2.06
76.5
1.99
72.0
2.12
76.5
2.05
72.0
2.18
76.5
2.10
72.0
2.24
76.5
2.16
72.0
2.29
76.5
2.19
72.0
2.33
76.5
2.22
72.0
2.36
76.5
2.25
72.0
2.40
76.5
2.33
72.0
2.48
76.5
2.36
72.0
2.52
76.5
2.41
72.0
2.59
76.5
2.47
72.0
2.63
76.5
2.64
72.0
2.86
76.5
2.80
72.0
3.03
76.5
3.16
72.0
3.41
76.5
3.34
72.0
3.62
76.5
3.53
72.0
3.83
76.5
3.91
72.0
4.23
76.5
4.33
72.0
4.70
76.5
4.65
72.0
5.06
76.5
5.05
72.0
5.50
76.5
5.59
72.0
6.11
76.5
Nominal capacity as rated: 0 ft. above sea level with 25 ft. of refrigerant piping.
0 ft. level difference between outdoor and indoor units.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and
67ºF wet bulb (WB), and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
88/73
91/76
PI
TC
PI
TC
kW
MBh
kW
MBh
1.77
86.1
1.96
95.1
1.86
86.1
2.07
95.1
1.94
86.1
2.15
95.1
2.01
86.1
2.23
95.1
2.07
86.1
2.29
95.1
2.14
86.1
2.38
95.1
2.21
86.1
2.46
95.1
2.27
86.1
2.53
95.1
2.33
86.1
2.61
95.1
2.39
86.1
2.68
95.1
2.45
86.1
2.74
95.1
2.48
86.1
2.78
95.1
2.52
86.1
2.82
95.1
2.56
86.1
2.88
95.1
2.64
86.1
2.96
95.1
2.68
86.1
3.02
95.1
2.75
86.1
3.11
95.1
2.80
86.1
3.16
95.1
3.07
86.1
3.53
95.1
3.27
86.1
3.76
95.1
3.67
86.1
4.24
95.1
3.90
86.1
4.51
95.1
4.14
86.1
4.79
95.1
4.58
86.1
5.31
95.1
5.09
86.1
5.93
95.1
5.48
86.1
6.39
95.1
5.97
86.1
6.70
95.1
5.87
80.9
5.08
80.4
PI
kW
2.17
2.29
2.38
2.47
2.54
2.63
2.73
2.82
2.90
2.98
3.05
3.10
3.14
3.19
3.32
3.37
3.48
3.55
4.03
4.30
4.86
5.16
5.48
6.10
6.82
7.35
7.55
5.74

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents