LG Multi V 5 Data Manual page 155

Hide thumbs Also See for Multi V 5:
Table of Contents

Advertisement

Outdoor air
Combination
temp.
(%)
TC
°F DB °F WB
MBh
-12.6
-13.0
385.5
-7.0
-7.6
419.8
-4.0
-4.4
440.5
0.0
-0.4
465.3
5.0
4.5
496.2
10.0
9.0
530.4
15.0
14.0
560.0
20.0
19.0
605.2
100%
25.0
23.0
643.8
30.0
28.0
674.6
35.0
32.0
685.8
40.0
36.0
685.8
45.0
41.0
685.8
47.0
43.0
685.8
50.0
46.0
685.8
55.0
51.0
685.8
60.0
56.0
685.8
-12.6
-13.0
383.8
-7.0
-7.6
418.1
-4.0
-4.4
438.6
0.0
-0.4
465.3
5.0
4.5
496.2
10.0
9.0
530.4
15.0
14.0
560.0
20.0
19.0
619.9
90%
25.0
23.0
628.8
30.0
28.0
628.8
35.0
32.0
628.8
40.0
36.0
628.8
45.0
41.0
628.8
47.0
43.0
628.8
50.0
46.0
628.8
55.0
51.0
628.8
60.0
56.0
628.8
-12.6
-13.0
382.2
-7.0
-7.6
416.3
-4.0
-4.4
436.8
0.0
-0.4
462.9
5.0
4.5
495.7
10.0
9.0
544.2
15.0
14.0
562.5
20.0
19.0
562.5
80%
25.0
23.0
562.5
30.0
28.0
562.5
35.0
32.0
562.5
40.0
36.0
562.5
45.0
41.0
562.5
47.0
43.0
562.5
50.0
46.0
562.5
55.0
51.0
562.5
60.0
56.0
562.5
TC = Total Capacity (MBh).
PI = Power Input (kW) (includes compressor and outdoor fan).
The System Combination Ratio must be between 50–130%.
Nominal capacity as rated: 0 ft. above sea level with 25 ft. of refrigerant piping.
0 ft. level difference between outdoor and indoor units.
59
61
64
PI
TC
PI
TC
kW
MBh
kW
MBh
37.1
385.5
38.78
385.5
40.87
419.8
42.54
419.8
43.14
440.5
44.81
440.5
45.93
464.4
47.60
462.9
49.42
496.2
51.10
496.2
52.91
529.0
54.59
526.8
56.33
560.0
58.02
560.0
60.65
603.0
61.57
599.7
64.73
634.7
62.07
621.1
60.30
654.0
58.09
623.2
55.88
660.7
54.09
623.2
51.47
660.7
50.09
623.2
47.14
660.7
46.18
623.2
45.90
660.7
44.94
623.2
44.20
660.7
43.29
623.2
41.48
660.7
40.63
623.2
38.58
660.7
37.79
623.2
36.72
383.8
37.98
383.8
40.49
418.1
41.76
418.1
42.76
438.6
44.02
438.6
45.56
464.4
46.81
462.9
49.05
496.2
50.31
496.2
52.55
529.0
53.80
526.8
55.97
560.0
57.23
560.0
61.17
599.7
59.93
569.3
57.53
605.1
56.38
569.3
53.91
605.1
52.82
569.3
50.27
605.1
49.26
569.3
46.64
605.1
45.70
569.3
43.07
605.1
42.20
569.3
41.92
605.1
41.08
569.3
40.38
605.1
39.56
569.3
37.89
605.1
37.13
569.3
35.24
605.1
34.54
569.3
31.94
382.2
33.02
382.2
35.72
416.3
36.8
416.3
37.98
436.8
39.06
436.8
40.77
462.9
41.86
462.9
44.27
495.7
45.35
495.7
47.75
530.8
48.84
510.6
51.65
541.8
52.27
510.6
52.40
541.8
51.47
510.6
49.24
541.8
48.36
510.6
46.08
541.8
45.24
510.6
42.90
541.8
42.13
510.6
39.74
541.8
39.00
510.6
36.64
541.8
35.95
510.6
35.67
541.8
34.98
510.6
34.35
541.8
33.69
510.6
32.24
541.8
31.63
510.6
29.98
541.8
29.42
510.6
©
HEATING CAPACITY DATA
ARUM504BTE5 / ARUM504DTE5
504,000 Btu/h 208-230V / 460V Outdoor Units
Indoor Air Temp. °F DB/°F WB
67
70
PI
TC
PI
TC
kW
MBh
kW
MBh
kW
41.29
384.3
43.05
383
44.81
45.06
418.5
46.82
417.2
48.58
47.32
439.1
49.09
437.7
50.85
50.13
462.3
51.88
461.7
53.64
53.61
494.8
55.37
493.5
57.14
57.12
526.6
58.87
526.2
60.63
60.53
558.6
60.78
557.3
61.05
62.97
583.3
60.40
567.0
57.83
58.11
594.0
56.38
567.0
54.67
54.76
595.1
53.13
567.0
51.51
51.40
595.1
49.87
567.0
48.34
48.05
595.1
46.61
567.0
45.17
44.73
595.1
43.38
567.0
42.04
43.54
595.1
42.24
567.0
40.93
41.94
595.1
40.67
567.0
39.42
39.36
595.1
38.18
567.0
37.01
36.60
595.1
35.51
567.0
34.40
39.87
382.6
41.95
381.4
44.02
43.65
416.7
45.73
415.5
47.79
45.91
437.3
47.98
435.9
50.06
48.70
462.0
50.77
461.1
52.85
52.19
494.4
54.27
492.6
56.33
55.69
521.7
57.76
516.6
59.84
59.11
539.7
58.41
519.2
57.71
58.09
544.3
56.27
519.2
54.44
54.64
544.3
52.94
519.2
51.23
51.19
544.3
49.60
519.2
48.01
47.74
544.3
46.28
519.2
44.81
44.30
544.3
42.94
519.2
41.60
40.90
544.3
39.67
519.2
38.44
39.82
544.3
38.62
519.2
37.42
38.35
544.3
37.19
519.2
36.04
35.99
544.3
34.91
519.2
33.83
33.47
544.3
32.47
519.2
31.46
34.66
381
37.12
379.8
39.57
38.44
415.1
40.89
413.7
43.34
40.70
435.5
43.15
434.1
45.61
43.50
459.6
45.95
456.1
48.40
46.99
480.4
49.44
465.0
51.90
50.48
487.8
51.26
465.0
52.04
53.20
487.8
51.24
465.0
49.30
50.09
487.8
48.26
465.0
46.43
47.04
487.8
45.33
465.0
43.63
43.99
487.8
42.40
465.0
40.82
40.93
487.8
39.47
465.0
38.02
37.89
487.8
36.55
465.0
35.21
34.89
487.8
33.68
465.0
32.47
33.97
487.8
32.79
465.0
31.59
32.72
487.8
31.58
465.0
30.43
30.71
487.8
29.63
465.0
28.57
28.56
487.8
27.56
465.0
26.56
Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and
outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
73
76
PI
TC
PI
TC
PI
MBh
kW
MBh
kW
383
48.26
383
50.24
417.2
52.02
417.2
54.02
437.7
54.28
437.7
56.28
461.7
57.09
461.7
59.08
493.5
60.58
493.5
62.56
520.1
62.65
507.0
61.63
533.7
59.98
502.4
58.16
533.7
56.53
502.4
54.80
533.7
53.13
502.4
51.49
533.7
49.74
502.4
48.19
533.7
46.35
502.4
44.89
533.7
42.96
502.4
41.60
533.7
39.64
502.4
38.35
533.7
38.58
502.4
37.33
533.7
37.15
502.4
35.95
533.7
34.87
502.4
33.75
533.7
32.43
502.4
31.38
381.4
47.87
381.4
51.03
415.5
51.65
415.5
54.79
435.9
53.91
435.9
57.05
459.9
56.71
457.3
59.85
480.9
58.67
461.7
58.54
488.7
57.53
459.0
54.95
488.7
54.58
459.0
52.11
488.7
51.51
459.0
49.16
488.7
48.49
459.0
46.26
488.7
45.47
459.0
43.36
488.7
42.45
459.0
40.45
488.7
39.44
459.0
37.56
488.7
36.48
459.0
34.70
488.7
35.51
459.0
33.78
488.7
34.20
459.0
32.53
488.7
32.09
459.0
30.53
488.7
29.85
459.0
28.40
379.8
44.81
379.8
47.96
413.7
48.36
413.7
51.03
427.5
50.50
412.9
52.88
435.9
52.34
410.3
52.70
436.1
51.23
410.2
49.66
436.1
48.67
410.2
47.16
436.1
46.17
410.2
44.71
436.1
43.56
410.2
42.15
436.1
41.02
410.2
39.64
436.1
38.46
410.2
37.13
436.1
35.90
410.2
34.63
436.1
33.35
410.2
32.12
436.1
30.83
410.2
29.66
436.1
30.02
410.2
28.87
436.1
28.92
410.2
27.81
436.1
27.14
410.2
26.10
436.1
25.24
410.2
24.28
PERFORMANCE DATA | 155
80
TC
Pl
MBh
kW
383
52.9
417.2
56.68
437.7
58.94
461.7
61.74
493.5
65.23
489.3
60.25
460.8
55.74
460.8
52.49
460.8
49.30
460.8
46.12
460.8
42.94
460.8
39.76
460.8
36.64
460.8
35.67
460.8
34.35
460.8
32.24
460.8
29.98
381.4
55.21
415.5
58.99
435.9
61.25
453.8
64.04
436.1
58.36
419.2
51.52
419.2
48.84
419.2
46.03
419.2
43.28
419.2
40.53
419.2
37.79
419.2
35.04
419.2
32.34
419.2
31.48
419.2
30.33
419.2
28.46
419.2
26.47
379.8
52.14
413.7
54.6
393.6
56.07
375.9
53.17
375.6
47.59
375.6
45.15
375.6
42.75
375.6
40.26
375.6
37.82
375.6
35.37
375.6
32.93
375.6
30.48
375.6
28.08
375.6
27.34
375.6
26.33
375.6
24.71
375.6
22.99