LG Multi V 5 Data Manual page 141

Hide thumbs Also See for Multi V 5:
Table of Contents

Advertisement

Outdoor air
Combination
temp.
(%)
TC
°F DB °F WB
MBh
-12.6
-13.0
291.2
-7.0
-7.6
312.9
-4.0
-4.4
325.9
0.0
-0.4
349.5
5.0
4.5
362.8
10.0
9.0
363.0
15.0
14.0
363.0
20.0
19.0
363.0
70%
25.0
23.0
363.0
30.0
28.0
363.0
35.0
32.0
363.0
40.0
36.0
363.0
45.0
41.0
363.0
47.0
43.0
363.0
50.0
46.0
363.0
55.0
51.0
363.0
60.0
56.0
363.0
-12.6
-13.0
268.2
-7.0
-7.6
289.6
-4.0
-4.4
308.8
0.0
-0.4
310.9
5.0
4.5
310.9
10.0
9.0
310.9
15.0
14.0
310.9
20.0
19.0
310.9
60%
25.0
23.0
310.9
30.0
28.0
310.9
35.0
32.0
310.9
40.0
36.0
310.9
45.0
41.0
310.9
47.0
43.0
310.9
50.0
46.0
310.9
55.0
51.0
310.9
60.0
56.0
310.9
-12.6
-13.0
260.1
-7.0
-7.6
260.1
-4.0
-4.4
260.1
0.0
-0.4
260.1
5.0
4.5
260.1
10.0
9.0
260.1
15.0
14.0
260.1
20.0
19.0
260.1
50%
25.0
23.0
260.1
30.0
28.0
260.1
35.0
32.0
260.1
40.0
36.0
260.1
45.0
41.0
260.1
47.0
43.0
260.1
50.0
46.0
260.1
55.0
51.0
260.1
60.0
56.0
260.1
TC = Total Capacity (MBh).
PI = Power Input (kW) (includes compressor and outdoor fan).
The System Combination Ratio must be between 50–130%.
Nominal capacity as rated: 0 ft. above sea level with 25 ft. of refrigerant piping.
0 ft. level difference between outdoor and indoor units.
59
61
64
PI
TC
PI
TC
kW
MBh
kW
MBh
23.63
291.2
24.94
291.2
26.56
312.9
27.87
312.9
28.32
325.9
29.62
325.9
30.48
341.9
31.78
330.5
33.19
349.9
34.49
330.5
35.90
350.0
37.20
330.5
40.42
350.0
39.29
330.5
37.79
350.0
36.73
330.5
35.20
350.0
34.22
330.5
32.61
350.0
31.71
330.5
30.01
350.0
29.21
330.5
27.42
350.0
26.70
330.5
24.92
350.0
24.26
330.5
24.25
350.0
23.62
330.5
23.36
350.0
22.75
330.5
21.92
350.0
21.35
330.5
20.38
350.0
19.86
330.5
24.01
268.2
25.24
268.2
26.94
287.5
28.17
284.3
28.69
299.0
29.92
284.3
30.85
300.3
32.09
284.3
33.57
300.3
34.80
284.3
38.07
300.3
37.51
284.3
36.99
300.3
35.93
284.3
34.50
300.3
33.47
284.3
32.07
300.3
31.07
284.3
29.64
300.3
28.66
284.3
27.22
300.3
26.26
284.3
24.79
300.3
23.85
284.3
22.43
300.3
21.52
284.3
21.84
300.3
20.95
284.3
21.03
300.3
20.18
284.3
19.74
300.3
18.94
284.3
18.36
300.3
17.61
284.3
21.68
250.5
23.63
236.3
24.6
250.5
26.55
236.3
26.35
250.5
28.31
236.3
28.53
250.5
30.48
236.3
33.20
250.5
33.18
236.3
34.71
250.5
33.23
236.3
32.37
250.5
31.00
236.3
29.94
250.5
28.67
236.3
27.55
250.5
26.39
236.3
25.17
250.5
24.11
236.3
22.77
250.5
21.83
236.3
20.39
250.5
19.55
236.3
18.09
250.5
17.36
236.3
17.62
250.5
16.90
236.3
16.97
250.5
16.28
236.3
15.93
250.5
15.28
236.3
14.82
250.5
14.21
236.3
©
HEATING CAPACITY DATA
ARUM384BTE5 / ARUM384DTE5
384,000 Btu/h 208-230V / 460V Outdoor Units
Indoor Air Temp. °F DB/°F WB
67
70
PI
TC
PI
TC
kW
MBh
kW
MBh
kW
26.89
290.3
28.97
289.4
31.05
29.81
306.6
32.09
300.3
34.37
31.57
313.1
33.96
300.3
36.36
33.73
315.4
36.27
300.3
38.81
36.45
315.4
37.56
300.3
38.68
39.15
315.4
37.84
300.3
36.52
37.59
315.4
36.00
300.3
34.41
35.15
315.4
33.68
300.3
32.21
32.77
315.4
31.41
300.3
30.05
30.37
315.4
29.14
300.3
27.90
27.99
315.4
26.87
300.3
25.74
25.60
315.4
24.60
300.3
23.58
23.29
315.4
22.38
300.3
21.49
22.67
315.4
21.79
300.3
20.92
21.83
315.4
20.99
300.3
20.15
20.49
315.4
19.70
300.3
18.91
19.06
315.4
18.32
300.3
17.59
27.1
262.9
29.53
257.6
31.95
30.02
271
32.5
257.6
31.78
271.0
34.27
257.6
36.75
33.94
271.0
35.55
257.6
37.15
36.65
271.0
35.86
257.6
35.07
36.66
271.0
34.82
257.6
32.98
34.34
271.0
32.64
257.6
30.94
31.92
271.0
30.37
257.6
28.82
29.55
271.0
28.14
257.6
26.74
27.19
271.0
25.92
257.6
24.65
24.81
271.0
23.69
257.6
22.57
22.45
271.0
21.47
257.6
20.49
20.16
271.0
19.32
257.6
18.47
19.63
271.0
18.80
257.6
17.98
18.90
271.0
18.11
257.6
17.32
17.74
271.0
17.00
257.6
16.25
16.50
271.0
15.80
257.6
15.12
26.55
225.6
29.03
215
31.53
29.48
225.6
30.99
215
32.5
31.23
225.6
32.75
215.0
34.25
33.40
225.6
33.19
215.0
32.98
33.15
225.6
32.05
215.0
30.96
31.03
225.6
29.98
215.0
28.94
28.94
225.6
27.96
215.0
26.96
26.78
225.6
25.83
215.0
24.90
24.67
225.6
23.77
215.0
22.88
22.54
225.6
21.70
215.0
20.86
20.42
225.6
19.63
215.0
18.84
18.29
225.6
17.55
215.0
16.82
16.25
225.6
15.57
215.0
14.87
15.82
225.6
15.16
215.0
14.48
15.25
225.6
14.59
215.0
13.94
14.30
225.6
13.69
215.0
13.09
13.30
225.6
12.74
215.0
12.17
Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and
outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
73
76
PI
TC
PI
TC
PI
MBh
kW
MBh
kW
282.6
35.16
267.9
37.63
283.8
37.7
267.5
39.19
283.8
39.22
267.5
40.12
283.8
38.95
267.5
38.29
283.8
36.88
267.5
36.18
283.8
34.80
267.5
34.07
283.8
32.77
267.5
31.99
283.8
30.66
267.5
29.83
283.8
28.58
267.5
27.71
283.8
26.51
267.5
25.60
283.8
24.44
267.5
23.49
283.8
22.37
267.5
21.36
283.8
20.36
267.5
19.32
283.8
19.82
267.5
18.80
283.8
19.09
267.5
18.11
283.8
17.91
267.5
17.00
283.8
16.66
267.5
15.80
242.5
36.18
229.2
38.72
35
242.5
36.73
229.2
38.35
242.5
37.28
229.2
36.33
242.5
35.83
229.2
34.61
242.5
33.75
229.2
32.55
242.5
31.68
229.2
30.50
242.5
29.65
229.2
28.49
242.5
27.53
229.2
26.39
242.5
25.46
229.2
24.34
242.5
23.38
229.2
22.29
242.5
21.31
229.2
20.23
242.5
19.24
229.2
18.18
242.5
17.23
229.2
16.20
242.5
16.78
229.2
15.77
242.5
16.16
229.2
15.19
242.5
15.17
229.2
14.26
242.5
14.10
229.2
13.26
202.3
33.25
190.6
34.88
202.3
33.68
190.6
32.03
202.3
32.46
190.6
30.87
202.3
30.95
190.6
29.42
202.3
29.06
190.6
27.62
202.3
27.17
190.6
25.81
202.3
25.33
190.6
24.04
202.3
23.40
190.6
22.19
202.3
21.51
190.6
20.38
202.3
19.63
190.6
18.58
202.3
17.73
190.6
16.77
202.3
15.85
190.6
14.96
202.3
14.04
190.6
13.23
202.3
13.66
190.6
12.89
202.3
13.16
190.6
12.41
202.3
12.35
190.6
11.64
202.3
11.49
190.6
10.83
PERFORMANCE DATA | 141
80
TC
Pl
MBh
kW
248.4
40.92
245.8
41.17
245.8
41.31
245.8
37.43
245.8
35.25
245.8
33.09
245.8
30.95
245.8
28.73
245.8
26.55
245.8
24.38
245.8
22.20
245.8
20.02
245.8
17.93
245.8
17.45
245.8
16.81
245.8
15.78
245.8
14.68
211.4
42.1
211.4
40.52
211.4
35.07
211.4
32.98
211.4
30.96
211.4
28.93
211.4
26.94
211.4
24.87
211.4
22.85
211.4
20.82
211.4
18.79
211.4
16.77
211.4
14.82
211.4
14.43
211.4
13.89
211.4
13.05
211.4
12.12
174.7
37.05
174.7
29.84
174.7
28.74
174.7
27.38
174.7
25.69
174.7
23.99
174.7
22.31
174.7
20.58
174.7
18.88
174.7
17.18
174.7
15.48
174.7
13.78
174.7
12.16
174.7
11.83
174.7
11.40
174.7
10.69
174.7
9.95