Honeywell L4064B Installation Instructions

Honeywell L4064B Installation Instructions

Universal combination fan and limit controllers
Hide thumbs Also See for L4064B:

Advertisement

Quick Links

L4064B, L4064R
Universal Combination Fan and
Limit Controllers
APPLICATION
These combination warm air fan and limit controllers
are suitable for various types of forced air heating
systems. The controllers have 2 switches; one which
opens the limit circuit if the plenum temperature
exceeds the preset safety limit; it resets automatically.
The other switch turns the fan on and off. The fan is
turned on and off according to plenum temperature.
The L4064R has a special high temperature range
suitable for gravity heating systems. All models may
be used as limit controllers by wiring only the limit
side. Limit contacts are suitable for both line voltage
and low voltage. For low voltage applications, the
brass jumper must be removed.
OPERATION
As the plenum temperature rises, the coiled bimetal
sensing element of the control warps and
mechanically makes the fan contacts (at the FAN ON
temperature setting). During normal operation, the
call for heat ends before the LIMIT setting is reached
and the fan contacts break as the plenum
temperature falls and the FAN OFF setting is reached.
If the call for heat continues until the temperature in
the plenum rises to the LIMIT setting, the bimetal
element will mechanically break the limit contacts
and de-energize the heating control circuit.
INSTALLATION INSTRUCTIONS
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to fol-
low them could damage the product or cause a
hazardous condition.
2. Check the ratings given in the instructions and
on the product to make sure the product is suit-
able for your application.
3. Installer must be a trained, experienced service
technician.
4. For 230 VAC application, use of double insu-
lated cable is required.
5. After installation is complete, check out product
operation as provided in these instructions.
WARNING
If limit switch is used on a low voltage
circuit, failure to remove brass jumper can
cause electrical shock hazard and/or
damage to low voltage controls.
CAUTION
1. Disconnect power supply before connecting
wiring to prevent electrical shock or equipment
damage.
2. When connecting cable or conduit to control,
avoid straining the control case.
Follow furnace or burner manufacturer's instructions,
if available. Maximum element temperature is:
L4064B—350 ºF (177 ºC).
L4064R—250 ºF (121 ºC) above limit setting.
Maximum switch temperature is:
L4064B,R—190 ºF (88 ºC).
69-0115-11

Advertisement

loading

Summary of Contents for Honeywell L4064B

  • Page 1 2. When connecting cable or conduit to control, avoid straining the control case. Follow furnace or burner manufacturer’s instructions, if available. Maximum element temperature is: L4064B—350 ºF (177 ºC). L4064R—250 ºF (121 ºC) above limit setting. Maximum switch temperature is: L4064B,R—190 ºF (88 ºC).
  • Page 2 L4064B, L4064R UNIVERSAL COMBINATION FAN AND LIMIT CONTROLLERS Surface Mounting (Fig. 1) Do not exceed the following electrical ratings (amperes): L4064B—Hole in plenum should be just large enough Table 1. Electrical Ranges to accommodate the 3/4 in.(19.1 mm) diameter element tube. A 13/16 in. (20.6 mm) diameter hole is...
  • Page 3 L4064B, L4064R UNIVERSAL COMBINATION FAN AND LIMIT CONTROLLERS WIRING Disconnect power supply before beginning installation to prevent electrical shock or equipment damage. All wiring must comply with local electrical codes and ordinances or in the absence of local codes with the National Electrical Code ANSI Cl-1981-NFPA 70.
  • Page 4 L4064B, L4064R UNIVERSAL COMBINATION FAN AND LIMIT CONTROLLERS CHECKOUT 3. Push male flag connector directly into the female receptacle. Make sure that the flag is forced to the bottom of cavity and wire is in the When installation is complete, disconnect the fan channel (Fig.