Avr Troubleshooting - Generac Power Systems 15 kW EcoGen Installation Manuallines

60 hz air-cooled generators
Hide thumbs Also See for 15 kW EcoGen:
Table of Contents

Advertisement

Troubleshooting
Table 8-2. Generator Troubleshooting (Continued)
Active Alarm
LED
UNDER
RED
VOLTAGE
UNDERSPEED
RED

AVR Troubleshooting

Table 8-3. AVR Troubleshooting
Ecode/Active
LED
Alarm
1048 VSCF
RED
Overload
1049 VSCF
RED
Overload
1051 VSCF High
YELLOW Yellow LED
Battery
1052 VSCF DC
RED
Overvoltage
1053 VSCF Gate
RED
Fault
1054 VSCF IGBT
RED
Overtemp.
40
Things to
Problem
Check
Unit will not start
in AUTO with
Check the
remote two-wire
LEDs/Screen for
start set to the ON
alarms.
(CLOSED)
position.
Unit will not start
in AUTO with
Check the
remote two-wire
LEDs/Screen for
start set to the ON
alarms.
(CLOSED)
position.
Things to
Problem
Check
Unit shuts down
Check the
during operation.
LEDs/Screen
for alarms.
Unit shuts down
Check the
during operation.
LEDs/Screen
for alarms.
Check the
illuminated in any
LEDs/Screen
state.
for alarms.
Unit shuts down
Check the
during operation.
LEDs/Screen
for alarms.
Unit shuts down
Check the
during operation
LEDs/Screen
or starting.
for alarms.
Unit shuts down
Check the
during operation
LEDs/Screen
or starting.
for alarms.
Contact Independent Authorized Servicing Dealer.
Contact Independent Authorized Servicing Dealer.
Possible Causes/Solution
Alternator, AVR or wiring is damaged.
Contact Independent Authorized Servicing Dealer.
Generator output is shorted or severely overloaded. Identify
and clear the overload, and then restart.
Voltage supply to the AVR is high. If an external battery
charger is in use, contact installing dealer to correct
installation. If an external battery charger is NOT in use,
contact Independent Authorized Servicing Dealer.
Probable causes are:
1) The generator was temporarily overloaded.
2) The output was temporarily shorted. Try to restart the unit.
AVR is damaged. Contact Independent Authorized Servicing
Dealer.
Probable causes are:
1) Replace AVR filter. Inspect fan.
2) Intake or exhaust air path is blocked. Check intake and
exhaust.
3) The BIG fan is not running (only runs when the engine is
running). KEEP FINGERS AWAY FROM FAN HOUSING-
PERSONAL INJURY CAN OCCUR IF FAN IS RUNNING.
Contact Independent Authorized Servicing Dealer.
4) Air leak in AVR enclosure. Contact Independent Authorized
Servicing Dealer.
5) Engine running too hot. Inspect air intake and exhaust.
6) Ambient temperature has risen above 140º F (60° C).
Derate the generator output per specifications.
Installation Guidelines For 60 Hz EcoGen™ Generators
Solution

Advertisement

Table of Contents
loading

Table of Contents