Ph/orp

Advertisement

3.1 System Power/Loop Connections
Stand-alone application, no current loop used
Transmitter
Terminals
Sys. Pwr.
2
Loop -
Sys. Pwr.
1
Loop +
Connection to a PLC/Recorder, separate supply
Transmitter
Terminals
Sys. Pwr.
2
Loop -
1
Sys. Pwr.
Loop +
3.2 Sensor Input Connections
Wiring Tips:
Do not route sensor cable in conduit containing AC power wiring. Electrical noise may interfere with sensor signal.
Routing sensor cable in grounded metal conduit will help prevent electrical noise and mechanical damage.
Seal cable entry points to prevent moisture damage.
Only one wire should be inserted into a terminal. Splice double wires outside the terminal.
Transmitter
≤ 400 ft. (122 m)
‡ SIGNET 8750-1 pH/ORP Transmitter
Power Supply
DC 12 - 24 V
-
Power
Supply
+
Power
Supply
DC 12 - 24 V
-
Power
Supply
+
Power
Supply
PLC or Recorder
-
Loop Input
4-20 mA in
+
Loop Input
4-20 mA in
White (Temp)
Terminals
12
Green (Temp)
11
Blue (ISO GND)
10
Brown (mV input)
9
*
8
Silver (Shield)
7
Black (V-)
6
Red (V+)
5
* (connection of terminal 8 to Earth GND
may reduce electrical interference)
Connection to a PLC with built-in power supply
Transmitter
Internal PLC
Connection
Terminals
Sys. Pwr.
2
Loop -
1
Sys. Pwr.
Loop +
Example: Two transmitter connected to PLC/Recorder
with separate power supply
Transmitter 1
Sys. Pwr.
2
Loop -
Sys. Pwr.
1
Loop +
Transmitter 2
Sys. Pwr.
2
Loop -
Sys. Pwr.
1
Loop +
PLC
Terminals
-
Power Supply
Ground
+
Power
Supply
-
Loop Input
4-20 mA
+
Loop Input
4-20 mA
DC 12 - 24 V
Power
-
Supply
Power
+
Supply
PLC or Recorder
-
Channel 1
4-20 mA in
+
Channel 1
4-20 mA in
-
Channel 2
4-20 mA in
+
Channel 2
4-20 mA in
Preamp:
+GF+ SIGNET 2720
pH Electrodes
+GF+ SIGNET 2714, 2714-HF
+GF+ SIGNET 2716
ORP Electrodes:
+GF+ SIGNET 2715
+GF+ SIGNET 2717
page 3 of 12