Configuration Mode Settings (continued)
4. Heat pump – Press the or button to configure as heat pump, or
non-heat pump system.
• ON = Heat pump system – 4 minute time delay with heat and cool
• OFF = Non-heat pump system – 4 minute time delay with cool only
Press the button to advance to the next screen.
5. Lockout (0-8°, NITE, COOL-HEAT) – Select the number of degrees set
temperature can be changed during keypad lockout or select to lockout during
NITE period only. COOL-HEAT lockout allows adjustment of the set temperatures
to the maximum heat set temperature selected in Step 6 and minimum cool set
temperature selected in Step 7.
Note: The mode cannot be changed when the thermostat is locked.
Press the or button to select.
Press the button to advance to the next screen.
6. Maximum Heat Setpoint
Adjust to control the maximum heat set temperature allowed.
Press the or button to select.
Press the button to advance to the next screen
7. Minimum Cool Setpoint
Adjust to control the minimum cool set temperature allowed.
Press the or button to select.
Press the button to advance to the next screen.
(45°F - 90°F) (7°C - 32°C)
(45°F - 90°F) (7°C - 32°C)