Menu Description
07
Domestic hot water hysteresis setting (i.e. number of
degrees below set point where the DHW will start
again)
08
Heating hysteresis setting (i.e number of degrees
below set point where the heating will start again)
09
Overheating of electronic expansion valve in heat-
ing mode
10
Overheating of electronic expansion valve in cooling
mode
11
Time delay for compressor start-up after power-up
(for example, after a power cut-off)
12
Circulation pump operation mode
13
Internal electrical heater operation during defrost-
ing
14
Automatic legionella protection function
15
Internal electrical heater start option
16
Air temperature restriction for when internal electri-
cal heater can manually be started, that is, must be
lower than this value.
17
Additional hysteresis in relation to menu 08 for
when internal electrical heater can manually be star-
ted.
18
Additional temperature hysteresis for hot water tank
electrical heater in relation to menu 07 for when the
electrical heater will start.
19
Hot water tank electrical heater startup delay
20
Return water temperature
21
Supply water temperature
22
Coil temperature in heating mode (T7)
23
Coil temperature in cooling mode (T8)
Danfoss Heating Solutions
DHP-AT
Default value
Range
5 °C
1—20 °C
2 °C
1—20 °C
2 °C
From -20 °C to +20 °C
3 °C
From -20 °C to + 20 °C
1 min*
1—10 min
1
1=Switched off when heating
temperature has been
reached.
0=Continuous operation
1
1= Turned on
0=Turned off
1
1=Activated
0=Deactivated
0
0=Auto
1=Air-temperature condition
set in menu 16
2=Water temperature condi-
tion set in menu 17
3= Conditions 1 and 2 must be
met
-5 °C
From -15 °C to +7 °C
2 °C
0—13 °C
5 °C
0—20 °C
30 min
30—90 min
Measured val-
From -30 °C to +99 °C
ue
Measured val-
From -30 °C to +99 °C
ue
Measured val-
From -30 °C to +99 °C
ue
Measured val-
From -30 °C to +99 °C
ue