Commissioning
▶ Check the new pipe section, including the seal at the gas train, for
external leaks.
The test pressure on the gas train inlet must be no higher than
150 mbar.
If a leak is discovered during this test, all connections
must be checked using a foaming agent. The agent must
be approved for gas tightness testing.
▶ Never allow the agent to come in contact with
electrical cables.
▶ Confirm in the commissioning report that the tightness test has been
carried out.
7.3

Recording gas parameters

Confirm gas parameters (Wobbe index and calorific value) and record
these in the commissioning report ( Chapter 7.18, page 28).
If the boiler is to be replaced in existing systems:
▶ Consult gas suppliers to ensure that the nominal gas
pressure according to Tab. 5 page 10 (country-
specific gas category and supply pressures) is
adhered to.
7.4

Check the system equipment level

The burner is supplied ready for use with a particular gas group or
subarea of a gas group as per the specifications of the delivery. This gas
group or its subarea must be present in the supply area. If you discover
Country:
AT, BE, CH, CZ, DE, DK, EE,
ES, FR, GB, HU, IE, IT, LT, LU,
LV, PL, PT, RO, RU, SI, SK,
TR, UA
DE, FR
NL
Tab. 10 Factory settings
22
Gas Type
Natural gas group H (G20)
Natural gas group E (G20)
Subarea Es of natural gas
group E (G20)
Natural gas group LL
Subarea Ei of natural gas
group E
Natural gas group L (G25)
that the boiler has been ordered with the wrong setting, the appliance
must be converted and the data plate updated accordingly.
▶ Check with the relevant gas supplier which gas group or subarea is
supplied.
▶ Compare the actual supply with the details indicated on the
appliance.
▶ If necessary, affix the label [2] (supplied with the boiler) that
corresponds to the supply over the appropriate area on the data plate
[1] (on the back panel).
Fig. 27 Updating the type plate
Factory settings
Factory-set ready for use.
The gas train is adjusted and sealed.
Upper Wobbe index for 15 °C, 1013 mbar:
3
• Adjusted to 14.1 kWh/m
• Applicable for 11.4 to 15.2 kWh/m
Upper Wobbe index for 0 °C, 1013 mbar:
3
• Adjusted to 14.9 kWh/m
• Applicable for 12.0 to 16.1 kWh/m
(Natural gas group "H according to DVGW Code of Practice G 260" falls within natural
gas group "E according to DIN EN 437")
Factory-set ready for use.
The gas train is adjusted and sealed.
Upper Wobbe index for 15 °C, 1013 mbar:
3
• Adjusted to 12.1 kWh/m
• Applicable for 11.4 to 12.4 kWh/m
Upper Wobbe index for 0 °C, 1013 mbar:
3
• Adjusted to 12.8 kWh/m
• Applicable for 12.0 to 13.1 kWh/m
(Natural gas group "L according to DVGW Code of Practice G 260" falls within natural
gas group "LL according to DIN EN 437")
Factory-set ready for use.
The gas train is adjusted and sealed.
Upper Wobbe index for 15 °C, 1013 mbar:
3
• Adjusted to 11.5 kWh/m
• Applicable for 10.85 to 12.4 kWh/m
Upper Wobbe index for 0 °C, 1013 mbar:
3
• Adjusted to 12.2 kWh/m
• Applicable for 10.6 to 13.8 kWh/m
3
3
3
3
3
3
Logano plus GB402 – 6 720 804 428 (2012/09)