Commissioning; Checking The Operating Pressure; Checking For Leaks - Buderus Logano plus GB402 Installation And Maintenance Instructions Manual

Floor standing gas condensing boiler
Table of Contents

Advertisement

Fig. 25 Gas connection
[1]
Anti vibration connection
[2]
Gas isolation valve (here with thermally activated shut-off
equipment)
[3]
Pipe clip
For higher gas supply pressures than shown in Tab. 11,
( page 24), Buderus offers additional gas pressure
regulators as accessories.
7

Commissioning

This Chapter describes commissioning using the standard control unit
module.
▶ After completing the work described below, complete the
commissioning report ( Chapter 7.18, page 28).
NOTICE: Boiler damage through excessive dust and dirt
contamination in open flue mode!
Strong dust and dirt contamination can occur, for
example, due to building work in the installation room.
▶ During building work, operate the boiler in balanced
flue mode.
NOTICE: Risk of boiler damage through contaminated
combustion air.
▶ Never use chlorinated cleaning agents or halogenated
hydrocarbons (as contained in spray cans, solvents,
cleaning agents, paints and adhesives, for example).
▶ Never store or use such substances in the installation
room.
▶ Never operate the boiler when there is a lot of dust, e.g. due to
building work. Never install air filters in the inlet path if there is a high
dust load. Convert the boiler to balanced flue operation if the dust
loads are excessive.
▶ Burners contaminated during building work must be cleaned before
commissioning.
▶ Inspect flue and combustion air pipework (with balanced flue
operation) and the apertures for combustion air supply and
ventilation ( Chapter 6.1, page 13).
Logano plus GB402 – 6 720 804 428 (2012/09)
7.1

Checking the operating pressure

This boiler cannot be operated with open vented heating
systems.
▶ Prior to commissioning, check the operating pressure of the heating
system on the water side and adjust if required.
NOTICE: System damage through boiler scaling!
▶ Note the information specified in the operator's log.
▶ Set the red needle [1] of the pressure gauge to the required operating
pressure of at least 1 bar.
2
1
Fig. 26 Pressure gauge for sealed unvented systems
[1]
Red needle
[2]
Pressure gauge needle
[3]
Green marking
CAUTION: Health risk through contaminated drinking
water.
▶ Always observe the regulations and standards
applicable in your jurisdiction for the prevention of
contamination of drinking water (e.g. by water from
heating systems).
▶ In Europe, observe standard EN 1717.
▶ Top up heating water or drain off water via the on-site drain & fill valve
until the required operating pressure has been reached.
▶ During filling, vent the heating system via the radiator bleed valves.
7.2

Checking for leaks

Prior to commissioning, check all new line sections on the gas side for
external gas tightness.
DANGER: Risk of explosion!
There is a risk of explosion if gas lines and gas
connections leak.
▶ Carry out an appropriate tightness test using
appropriate means.
DANGER: Risk of system damage due to short circuit!
▶ Cover the areas at risk before performing a tightness
test, e.g. the internal water pressure sensor and the
return sensor on the boiler return.
▶ Never spray or let leak detection agent drip onto cable
entries, plugs or electrical cables/leads.
Commissioning
7
3
6 720 615 876-59.1RS
21

Advertisement

Table of Contents
loading

Table of Contents