6.2

Recording gas parameters

Check the gas parameters (Wobbe index and calorific
value) with the relevant gas supply utility and enter them
in the commissioning report (
6.3

Check the system equipment level

In its delivered condition, the burner is set up to be
operated with natural gas H or L.
Country:
AT, BA, BE, BG, BY,
CH, CN, CZ, DE, DK,
EE, ES, FR, GB, GR,
HR, HU, IE, IT, LU, LT,
LV, NO, PL, PT, RO,
RU, SE, SI, SK, UA
DE
NL
Tab. 14 Factory settings
Logano plus GB312 - Subject to technical modifications.
Chapter 6.23).
Gas type
Factory settings
Natural gas H or E
Factory-set ready for use.
(G20)
The gas train is adjusted and sealed.
Wobbe index for 15 °C, 1013 mbar:
• Adjusted to 14.1 kWh/m
• Applicable for 11.4 to 15.2 kWh/m
Wobbe index for 0 °C, 1013 mbar:
• Adjusted to 14.9 kWh/m
• Applicable for 12.0 to 16.1 kWh/m
Natural gas L
Factory-set ready for use.
The gas train is adjusted and sealed.
Wobbe index for 15 °C, 1013 mbar:
• Adjusted to 12.1 kWh/m
• Applicable for 11.4 to 12.4 kWh/m
Wobbe index for 0 °C, 1013 mbar:
• Adjusted to 12.8 kWh/m
• Applicable for 12.0 to 13.1 kWh/m
Natural gas L (G25)
Factory-set ready for use.
The gas train is adjusted and sealed.
Wobbe index for 15 °C, 1013 mbar:
• Adjusted to 11.5 kWh/m
• Applicable for 10.85 to 12.4 kWh/m
Wobbe index for 0 °C, 1013 mbar:
• Adjusted to 12.2 kWh/m
• Applicable for 10.6 to 13.8 kWh/m
Only use the burner with the correct gas
nozzles.
B Check with the relevant gas supply utility which gas
type is supplied.
B Check whether the actual gas type is the same as that
stated on the type plate.
3
3
3
3
3
3
Commissioning
3
3
3
3
3
3
6
29