Troubleshooting Indoor Unit Error Codes - Lennox MPA009S4S Service Manual

Mini-split systems
Table of Contents

Advertisement

25. Troubleshooting Indoor Unit Error Codes

Error Code:
CP
Description:
MWMA models only.
General Note:
None.
This S4 jumper is on the adapter
board. There needs to be a
jumper in place . If jumper is
there then make sure it is making
good contact.
Error Code:
E0
Description:
Indoor Unit EEPROM malfunction.
General Note:
PCB main chip does not receive feedback from EEPROM chip.
Shut off the power supply and turn it on 1 min-
ute later. Is it still displaying the error code?
If the EEPROM chip is soldered on PCB, re-
place the PCB. Otherwise, check whether the
EEPROM chip is plugged in PCB properly?
Replace the indoor PCB.
Adapter board
located on door
of MWMA unit
E0
Yes
Yes
The unit will show "CP" if the cap
missing or not making contact.
Need to make sure the two pin to
making contact with the jumper.
No
Insert the EEPROM properly
128
Adapter board
The Cap

Hide quick links: