Master Reset (P999)

Note:
Following a Master Reset, complete programming is required.
Resets all parameters to their factory settings, with the following exceptions:
P000 and P069 are not reset.
The learned TVT curve is not lost.
Press PROGRAM
1.
2.
Press DISPLAY
3.
Key in 999.
Press CLEAR
and initiate reset. The LCD displays C.ALL.
4.
Reset complete. (Reset takes several seconds
to complete.)

Using Units or Percent (%)

Many parameters can be viewed either as a percentage, or in measurement units (P005).
View the parameter, then press MODE

Setup Steps (outline)

Set the Quick Start parameters between P001 and P010 (the main settings that apply to all
applications and make the system operational). Then set P837 and 838 to ignore false
echoes, and return to RUN mode.
1.
Select a language option
2.
Select the measurement mode: level, space, or distance (P001).
3.
Set the response time to level changes (P003).
4.
Select units of measurement: m, cm, mm, ft, or in. (P005).
5.
Set process empty level (Empty: P006).
6.
Set the range to be measured (Span: P007).
7.
To ignore false echoes before the material echo, set Auto False-Echo Suppression
Distance P838.
8.
Enable Auto False-Echo Suppression P837.
9.
Return to RUN mode.
1.
The language options are English, German, French, or Spanish. The parameter title appears in
the language selected, for the first 10 parameters.
7ML19985HT01
then DISPLAY
to open parameter fields.
then ENTER
, to Clear All
1
, or numeric, for the auxiliary reading (P010).
SITRANS Probe LU – INSTRUCTION MANUAL
to activate PROGRAM mode.
to toggle between units and percentage.
Page 19