Installation

WARNING: This product can only function properly and safely if it is
correctly transported, stored, installed, set up, operated and
maintained.
Notes:
Installation shall only be performed by qualified personnel and in accordance with
local governing regulations.
This product is susceptible to electrostatic shock. Follow proper grounding
procedures.
Ideally, mount SITRANS Probe LU so that the face of the transducer is at least 300
mm (1 ft) above the highest anticipated level.
Mounting Location
Recommendations:
Ambient temperature within –40 to 80
Easy access for viewing the display and programming via the hand programmer.
An environment suitable to the housing rating and materials of construction.
Keep the sound path perpendicular to the material surface.
.
ambient temperature
surrounding enclosure
o
–40 to 80
C (–40 to 176
process temperature
o
–40 to 85
C (–40 to 185
7ML19985HT01
SITRANS Probe LU – INSTRUCTION MANUAL
o
F)
o
F)
o
o
C (–40 to 176
F).
flange adaptor (option)
customer-supplied
flange
Page 9